Preparing for Installation
High Voltage
Single Phase
Comments
Usable PDU power cord length
2 m (6.6 feet)
PDU power cords are 4 m long (13 feet), but
sections are used for internal routing in the
rack.
Related Information
■
“Facility Power Requirements” on page 100
■
“Grounding Requirements” on page 100
■
“System Power Consumption” on page 290
Preparing for Cooling
■
“Environmental Requirements” on page 293
■
“Heat Dissipation and Airflow Requirements” on page 294
■
“Perforated Floor Tiles” on page 296
Environmental Requirements
The following table lists temperature, humidity and altitude requirements.
TABLE 65
Temperature, Humidity, and Altitude
Condition
Operating Requirement
Non-operating Requirement
Comments
Temperature
5 to 32°C (41 to 89.6°F)
-40 to 70°C (-40 to 158°F).
For optimal rack cooling, data
center temperatures from 21 to
23°C (70 to 47°F)
Relative humidity
10 to 90% relative humidity,
noncondensing
Up to 93% relative humidity.
For optimal data center
rack cooling, 45 to 50%,
noncondensing
Altitude
3048 m (10000 ft.) maximum
12000 m (40000 ft.).
Ambient temperature is reduced
by 1 degree Celsius per 300 m
above 900 m altitude above sea
level
Related Information
■
“Heat Dissipation and Airflow Requirements” on page 294
■
“Perforated Floor Tiles” on page 296
Connecting Expansion Racks
293
Summary of Contents for SuperCluster T5-8
Page 1: ...Oracle SuperCluster T5 8 Owner s Guide Part No E40167 17 May 2016 ...
Page 2: ......
Page 11: ...Contents Index 353 11 ...
Page 12: ...12 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 14: ...14 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 116: ...116 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 204: ...204 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 228: ...228 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 244: ...244 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...