Understanding Expansion Rack Internal Cabling
TABLE 78
Single-Phase PDU Cabling for the Expansion Rack (Half Rack)
Rack Unit
PDU-A/PS-00
PDU-B/PS-01
Cable Length
U24
G3-1
G2-5
2 meters
U23
N/A
G3-0
included
U22
G2-5
G3-1
1 meter
U21
G3-0
G2-6
2 meters
U20
G2-4
G3-2
2 meters
U18
G2-2
G3-4
2 meters
U16
G1-6
G4-0
2 meters
U14
G2-0
G3-6
2 meters
U12
G1-4
G4-2
2 meters
U10
G1-2
G4-4
2 meters
U8
G1-0
G4-6
2 meters
U6
G0-6
G5-0
2 meters
U4
G0-4
G5-2
2 meters
U2
G0-2
G5-4
2 meters
TABLE 79
Single-Phase PDU Cabling for the Expansion Rack (Quarter Rack)
Rack Unit
PDU-A/PS-00
PDU-B/PS-01
Cable Length
U24
G3-1
G2-5
2 meters
U23
N/A
G3-0
included
U22
G2-5
G3-1
1 meter
U21
G3-0
G2-6
2 meters
U20
G2-4
G3-2
2 meters
U8
G1-0
G4-6
2 meters
U6
G0-6
G5-0
2 meters
U4
G0-4
G5-2
2 meters
U2
G0-2
G5-4
2 meters
Three-Phase Power Distribution Unit Cabling
This topic contains tables that list the three-phase cabling from each PDU to the power supplies
configured in each rack. The cables are terminated to PDU-A on the left, and routed to the right
to enter CMA, and are bundled in groups of four.
■
Table 80, “Three-Phase PDU Cabling for the Expansion Rack (Full Rack),” on page 310
■
Table 81, “Three-Phase PDU Cabling for the Expansion Rack (Half Rack),” on page 310
Connecting Expansion Racks
309
Summary of Contents for SuperCluster T5-8
Page 1: ...Oracle SuperCluster T5 8 Owner s Guide Part No E40167 17 May 2016 ...
Page 2: ......
Page 11: ...Contents Index 353 11 ...
Page 12: ...12 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 14: ...14 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 116: ...116 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 204: ...204 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 228: ...228 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 244: ...244 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...