7
EN
3.2
Setup of the wood burning stove
Fire safety regulations according to Feu-
Vo
(minimum distances; see Fig. 2) must be
complied with when setting up the appliance.
FeuVo
("Ordinance on Firing Installations and
Fuel Storage", or: Firing Ordinance for short)
is the legal basis for setting up and operating
firing installations.
Caution!
For your own safety, you
must comply with the mini-
mum distances specified to
installation walls, flammable
furnishings and objects and
for protection of the flooring!
Note:
Before heating the system for
the first time, please remove
all documents and accessory
parts from the firebox and
ash box.
Remove all stickers so there
is no residue from the view-
ing pane.
Fig. 2
Caution!
Ensure before setup that the
floor (setup surface)
is able to support the weight
of the stove. If necessary,
use a suitable supporting
plate to distribute the weight.
The rear (B1) and side (B2) minimum distanc-
es are also listed on your stove's type plate.
A:
80 cm in the radiant range of the pane
B1:
20 cm distance from the wall at the rear
B2:
80 cm distance from the wall at the side
C:
30 cm floor protection on the side of the
filler opening
D:
50 cm floor protection in front of the
filler opening
Minimum distances that must be main-
tained: