INSTALLATION, OPERATION AND MAINTENANCE MANUAL
MODEL
RR & RC
FLAP GATES
TROUBLE SHOOTING
SYMPTOM
CAUSE
SOLUTION
Leakage between flap
gate and concrete wall
Concrete wall does not
meet the required std.
Un-install the slide gate and fix
the wall.
Not enough construction
sealant.
Un-install the slide gate, clean
the wall and apply a new layer of
construction sealant.
Loose anchor bolts.
Tighten anchor bolts.
Incorrect anchor bolts.
Check the “General Arrangement
Drawing” and make sure the
right anchor bolts have been in-
stalled.
Leakage through the seal
Foreign material trapped
between flap and frame
Remove the foreign material.
Check if there is any damage to
the seal.
Damaged seal.
Replace seal.