26
| USER GUIDE
OMR 700
6.
TECHNICAL DATA
IN.5 - 5x RTD INPUT
Number of inputs
5
Galv. separation
no
Type Pt
EU > 100/500/1 000 Ω, with 3 850 ppm/°C
Type Ni
Ni 1 000/ Ni 10 000 with 6 180 ppm/°C
Type Cu
Cu 50/Cu 100 with 4 280 ppm/°C
Connection
2, 3 or 4-wire
Range
EU • Pt xxxx
-50°…450°C
US • Pt 100
-50°…450°C
RU • Pt 50
-200°…1 100°C
RU • Pt 100
-200°…450°C
Cu 100/4 280
-200°…200°C
Cu 100/4 260
-50°…200°C
Ni • Ni xxxx
-50°..250°C
TC
25 ppm/°C
Accuracy
±0,2 % of the range
Rate
1 000 measuring/s
Recomm. positions
A1, A2, A3, A4
IN.6 - 12x CURRENT INPUT
Number of inputs
12
Galv. separation
no
Range
±5 mA
< 200 mV
±20 mA
< 200 mV
4...20 mA
< 200 mV
TC
25 ppm/°C
Accuracy
±0,2 % of the range
Rate
1000 measuring/s
Recomm. positions
A1, A2, A3, A4
IN.7 - 12x VOLTAGE INPUT
Number of inputs
12
Galv. separation
no
Range
±2 V
> 10 MΩ
±5 V
1,25 MΩ
±10 V
1,25 MΩ
±40 V
1,25 MΩ
TC
25 ppm/°C
Accuracy
±0,2 % of the range
Rate
1000 measuring/s
Recomm. positions
A1, A2, A3, A4
IN.8 - 2x INPUT FOR STRAIN GAUGES
Number of inputs
2
Galv. separation
yes
Range
0,5…2 mV/V
1…4 mV/V
2…8 mV/V
4…16 mV/V
Sensor supply
10 VDC, load ≥ 80 Ω
TC
25 ppm/°C
Accuracy
±0,05 % of the range
Rate
1 000 measuring/s
Recomm. positions
A1, A2, A3, A4
IN.9 - 3x PRECISE PM INPUT U-I
Number of inputs
3
Galv. separation
yes
Range
±5 mA
< 200 mV
±20 mA
< 200 mV
4...20 mA
< 200 mV
±2 V
> 10 MΩ
±5 V
1,25 MΩ
±10 V
1,25 MΩ
±40 V
1,25 MΩ
TC
25 ppm/°C
Accuracy
±0,02 % of the range
Rate
1 000 measuring/s
Recomm. positions
A1, A2, A3, A4
IN.11 - 8x ANALOGUE/DIGITAL INPUT
Number of inputs
8
Galv. separation
no
Range
12…250 V AC/DC
TC
25 ppm/°C
Accuracy
±0,5 % of the range
Rate
< 1 000 measuring/s
Recomm. positions
A1, A2, A3, A4
IN.12 - 12x PULSE INPUT
Number of inputs
12
Galv. separation
no
Range
5…30 VDC
Input
PNP/NPN/contact,
adjustable comparation levels
Frequency
0,1 Hz…10 kHz
Mode
Counter/Frequency
TC
25 ppm/°C
Accuracy
±0,01 % of the range (Frequency)
Recomm. positions
A1, A2, A3, A4
IN.13 - 2x FAST PULSE INPUT
Number of inputs
2
Galv. separation
yes
Range
5/24 VDC
Input
PNP/NPN/contact, TTL/line
adjustable comparation levels
Frequency
0,1 Hz…1 MHz
Mode
UP/DW Counter/Frequency IRC
Sensor supply
5/10/12/24 VDC/200 mA
TC
25 ppm/°C
Accuracy
±0,01 % of the range (Frequency)
Recomm. positions
A1, A2, A3, A4
IN.14 - 2x INPUT FOR LVDT SENSORS
Number of inputs
2
Galv. separation
yes
Input
3/5/6 -wire connection
1/3/5 VAC with frequency 2,5/5/10 kHz
TC
25 ppm/°C
Accuracy
±0,02 % of the range (Kmitočet)
Recomm. positions
A1, A2, A3, A4