4. INSTRUMENT SETTING - CONFIGURATION MODE
4.2.1.3.2 SHIFTING THE BEGINNING OF THE RANGE
RTD
OHM
+
CHA.
SER.
OUT.
CL. T.
AUX.
CFG
KEY
INP.
M.P.S.
MOD
LEA.
R. Ad.
A. ST.
R. Ad.
Shifting the beginning of
the measuring range
- in cases when it is necessary to shift the
beginning of the range by a given value, e.g.
when using sensor in measuring probe
- entered directly in Ohm
4.2.1.3.3 COMPENSATION OF 2-WIRE CONDUCT
RTD
OHM
A. ST.
+
CHA.
SER.
OUT.
CL. T.
AUX.
CFG
KEY
INP.
M.P.S.
MOD
LEA.
r. Ad.
YES
LEA.
Compensation of 2-wire
conduct
- for measurement accuracy it is always
necessary to perform compensation of the
conduct in case of 2-wire connection
- entered directly in Ohm
- prior to confirmation of the displayed
challenge „YES“ it is necessary to substitute
the sensor at the end of the conduct by a
short circuit
- preset from manufacture to „0“
4.2.1.3.4 SETTING THE MODE OF ASSESSMENT OF CJC
T/C
+
IN. 1
Ex. 2
Ex. 1
IN. 2
CHA.
SER.
OUT.
CL. T.
AUX.
CFG
KEY
INP.
M.P.S.
MOD
T.C.J.
CJC
C.J.C.
Mode of assessment of
cold junction
- description of the mode of assessment of cold
junction is in chapter 5, page 30
IN. 1
Measurement without
reference thermocouple
- CJC measurement on the instrument brackets
IN. 2
Measurement with reference
thermocouple
- cold junction measurement on the instrument
brackets with anti-series connection of ref.
thermocouple
Ex. 1
Measurement without
reference thermocouple
- whole measuring system operates under
identical and constant temperature
Ex. 2
Measurement with reference
thermocouple
- when using compensation box