SUGGESTED WIRING TO BE PERFORMED BY LICENSED ELECTRICIAN IN ACCORDANCE WITH ALL APPLICABLE LOCAL, STATE, & FEDERAL REQUIREMENTS.

Electrical Installation Diagram

Junction Box

Metal Double Gang

Junction Box

Cover

Carlon Blue Single

All Components

Readily Available

at Electronic &

Home Super Stores.

Thermostat and Controls:

Always install the thermostat for

your floor warming system per local code and per manufacturers
instructions. When using a thermostat with a floor sensor, it is important
to make sure that the floor sensor is placed 1-3’ out into the heated floor
and centered between two cable runs (See Electrical Installation Diagram
below). The floor sensor must be embedded in the pour. Where cable
system total amp load is greater than 15, an RFWCK Series Control Box
is available. When using an RFWCK Series Control Box, GFCI
Protection is required at the breaker.

FW.INST.Ver.2.0210R

Conduit to GFCI or

standard breaker

power source as

required

½”Conduit for floor

sensor only

Double Gang

Metal Box

Electrical conduit

sized per code

Heating cable

CABLE AMPERAGE

DRAW MUST NOT

EXCEED 15 AMPS

CABLE AMPERAGE

DRAW MUST NOT

EXCEED 15 AMPS

Metal, double gang

wall box

Box must be grounded.

To Floor Sensor

(Polarity is not important)

SENSOR

Caution:

Supply the TXLP/2R Heating cable

with the voltage it was tagged with at the factory

NEVERCUTTHEHEATINGCABLE

Caution:

Supply the TXLP/2R Heating cable

with the voltage it was tagged with at the factory

NEVERCUTTHEHEATINGCABLE

THERMOSTAT WIRING DIAGRAM

THERMOSTAT WIRING DIAGRAM

THERMOSTAT

120/240 LINE VOLTAGE, 15 AMP MAX. LOAD

120/240 LINE VOLTAGE, 15 AMP MAX. LOAD

The Power Leads

For The Thermostat

If the voltage of the

cable is 120 volt

To Floor Sensor

(Polarity is not important.)

IMPORTANT:

DO NOT MIX VOLTAGES

The supply

voltage used for the
heating cable should be
the same voltage used
for the thermostat.

Consult Manufacturers

Instructions For Specific

Wiring Details.

The Power Leads

For The Thermostat

If the cable is 220, 230,

or 240 volt

Red Wire

Black Wire

Panel

220, 230 or 240 Volt

Circuit Breaker

Circuit Breaker Panel

White Wire

Black Wire

120 Volt

Circuit Breaker

Panel

To The Neutral Buss in the Circuit Breaker Panel

Bare Copper Wire

Ground

Clear Insulated Wires

TXLP/2R Heating Cable

Uninsulated, ‘Cold End’

Ground Lead

Cold Lead

Bulb