9
Fitting and maintenance instructions HRC 300/400 4B(P/RH)
Dipswitch setting HRC 400 4B(P/RH)
ON
1 2
ON
5 6 7 8
ON
ON
ON
ON
ON
ON
ON
ON
ON
1 2
ON
ON
ON
ON
ON
3 4
3 4
ON
ON
ON
ON
ON
1 = OFF, 2 = ON
105 m
3
/h
5 = OFF, 6 = OFF, 7 = OFF, 8 = OFF
245 m
3
/h
5 = OFF, 6 = ON, 7 = OFF, 8 = OFF
270 m
3
/h
5 = OFF, 6 = OFF, 7 = OFF, 8 = ON
280 m
3
/h
5 = OFF, 6 = ON, 7 = ON, 8 = OFF
310 m
3
/h
3 = ON, 4 = OFF
150 m
3
/h
5 = ON, 6 = OFF, 7 = OFF, 8 = ON
330 m
3
/h
5 = OFF, 6 = ON, 7 = OFF, 8 = ON
345 m
3
/h
5 = OFF, 6 = ON, 7 = ON, 8 = ON
370 m
3
/h
5 = ON, 6 = ON, 7 = OFF, 8 = ON
390 m
3
/h
1 = ON, 2 = ON
120 m
3
/h
5 = ON, 6 = OFF, 7 = OFF, 8 = OFF
255 m
3
/h
5 = OFF, 6 = OFF, 7 = ON, 8 = OFF
275 m
3
/h
5 = ON, 6 = ON, 7 = OFF, 8 = OFF
295 m
3
/h
5 = OFF, 6 = OFF, 7 = ON, 8 = ON
320 m
3
/h
3 = OFF, 4 = ON
180 m
3
/h
5 = ON, 6 = OFF, 7 = ON, 8 = OFF
340 m
3
/h
5 = ON, 6 = ON, 7 = ON, 8 = OFF
355 m
3
/h
5 = ON, 6 = OFF, 7 = ON, 8 = ON
380 m
3
/h
5 = ON, 6 = ON, 7 = ON, 8 = ON
400 m
3
/h
3 = ON, 4 = ON
215 m
3
/h
Low
High
Middle
3 4
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
5 6 7 8
Factory setting:
L = 120m
3
/h
M = 180m
3
/h
H = 275m
3
/h
ON
1 2 3 4 5 6 7 8