Connecting condensate drain (TA series)
The condensation water must be drained off to prevent water damage to the unit or
ducts. The hose connection is located underneath the unit. A reinforced hose with
an internal diameter of 10 mm and a maximum length of 1.5 m must be connected
to this. The condensation water must be drained via a siphon into the sewerage
system, see diagram below.
Then fit the condensation drain hose into the hose connection; the condensation drain
must not be kinked. Pour water into the drip tray to create a water trap and also check
the condensate drain for leaks.
Points of attention:
1. A hose clamp should be used so that the drain can be easily dismantled
and cleaned later.
2. The drain hose must be placed at an angle and may not kink, so that the water
can drain off easily. It is absolutely forbidden to connect the hose directly to the
sewage system (because of odours).
Bottom view Side view