Information
5 T
112
Information item
Information bit output
signal
Cause
Reset condition
Odometer
INFO-ODO
The cumulative travel distance of the motor
exceeded the value set in the "Odometer
information" parameter.
After the following operation was
performed, the cumulative travel
distance (Odometer) of the motor
fell below the value set in the
"Odometer information” parameter.
The "Odometer information"
parameter was set again.
Start operation
restricted mode
INFO-DSLMTD
•
"Teaching, remote operation" was executed
using the
MEXE02
software.
•
Configuration was executed.
•
Data was written to the driver from the
MEXE02
software.
•
”Restored to the factory setting” was
executed using the
MEXE02
software.
•
Teaching, remote operation was
released.
•
Configuration was completed.
•
Writing data was completed.
•
Data was restored to the factory
setting.
I/O test mode
INFO-IOTEST
•
“I/O test” was executed with the
MEXE02
software.
•
Configuration was executed.
•
The I/O test mode was canceled.
•
Configuration was completed.
Configuration
request
INFO-CFG
The parameter that required executing the
configuration was changed.
Configuration was executed.
Reboot request
INFO-RBT
The parameter that required rebooting was
changed.
Reboot was executed.
If the "Preset request" information was generated for 100 ms or more in a state where the
"Information auto clear" parameter was set to disable, the preset may have been failed. There are the
following two possible reasons that the preset was failed.
- The ABZO sensor is not connected to the driver.
- The preset was executed in a state where the position deviation between the command position
and the feedback position was 1.8° or more.