Q I G
Quick Installation Guide
PRINTED ON RECYCLED PAPER
Q
uick
I
nstallation
G
uide
Q I G
The device can be connected to a serial device using a DB9 cable. The DB9
connector supports RS-232 / RS-422 / RS-485 operation modes. Please refer to
the following table for the pin assignments of the DB9 connector.
Wiring
The device has two sets of power inputs in the form of DC power jack and terminal.
The power input connectors are located on the top panel alongside the Ethernet
port. Follow the steps below to wire the power input on the terminal block.
Step 1: insert the negative / positive wires into the V-/V+ terminals, respectively.
Step 2: to keep the wires from pulling loose, use a small flat-blade screwdriver to
tighten the wire-clamp screws on the front of the terminal block connector.
Power inputs
Grounding and wire routing help limit the effects of noise due to electromagnetic
interference (EMI). Run the ground connection from the ground screws to the grounding
surface prior to connecting devices.
Grounding
Configurations
After installing the device, the green power LED should turn on. Please refer
to the following tablet for LED indication.
Environmental
-40 to 85 C (-40 to 185 F)
o
o
Storage Temperature
Operating Temperature
-40 to 85 C (-40 to 185 F)
o
o
5% to 95% Non-condensing
Operating Humidity
Regulatory Approvals
FCC Part 15, CISPR (EN55022) class A
EMI
EN61000-4-2 (ESD)
EN61000-4-3 (RS)
EN61000-4-4 (EFT)
EN61000-4-5 (Surge)
EN61000-4-6 (CS)
EN61000-4-8
EN61000-4-11
EMS
IEC60068-2-27
Shock
IEC60068-2-32
IEC60068-2-6
Vibration
EN60950-1
Safety
Free Fall
Warranty
5 years
IEC 61850-3, IEEE 1613
Power Automation
Oring Device Model
10/100 Base-T(X) Ports in RJ45
Auto MDI/MDIX
1
Physical Ports
Serial Ports
TxD, RxD, RTS, CTS, DTR, DSR, DCD, RI, GND
RS-232
RS-422
Power
Redundant Input power
Power consumption(Typ.)
Overload current protection
Reverse polarity protection
Present
Present on terminal block
Physical Characteristic
Enclosure
IP-30
Dimension (W x D x H)
72(W)x29.4(D)x123.4(H) mm (2.83x1.16x4.86 inch.)
Weight (g)
Stop Bits
1, 1.5, 2
Tx+, Tx-, Rx+, Rx, GND
294g
Data Bits
5, 6, 7, 8
Parity
odd, even, none, mark, space
RS-485 (4-wire)
RS-485 (2-wire)
Data+, Data-,GND
Flow Control
XON/XOFF, RTS/CTS, DTR/DSR
Network Protocol
Protocol
ICMP, IP, TCP, UDP, DHCP, BOOTP, DNS, SNMP V1/V2c, HTTPS, SMTP, DDNS, PPPoE, Modbus TCP
IDS-M311
Dual DC inputs. 12-48VDC on 3-pin terminal block and power jack
4 watts
Specifications
DB9 serial port
1 2 3
4 5
6 7 8 9
LED
Color
Status
Description
On
Power module 1 activated
Red
Blinking
DHCP servers do not respond properly
PW1/2
Green
On
Power is on and function normally
Green
On
Port running at 100Mbps
ETH
LNK/ACT
Amber
On
Port running at 10Mbps
Red
On
Receiving data
TX / RX
Green
On
Transmitting data
ORing Industrial Networking Corp.
Copyright© 2014 ORing
All rights reserved.
TEL: +886-2-2218-1066
FAX: +886-2-2218-1014
Website: www.oring-networking.com
E-mail: support@oring-networking.com
Pin #
RS
-
232
RS
-
422
RS
-
485
( 4 wire )
RS
-
485
( 2 wire )
1
DCD
RXD -
RXD -
2
RXD
RXD +
RXD +
3
TXD
TXD +
TXD +
DATA +
4
DTR
TXD -
TXD -
DATA -
5
GND
GND
GND
GND
6
DSR
7
RTS
8
CTS
9
RI
RS
-
232 mode act as DTE
Serial Baud Rate
110 bps to 115.2 Kbps
Connector
DB9 (male) x 1
Operation Mode
RS-232 / RS-422 / 4(2)-Wire RS-485. Which can be configured by Web interface
Tx+, Tx-, Rx+, Rx, GND
Version 1.0
IDS-M311
IDS-M311
Industrial Device Server
Device
Server
Device
Server