APPENDIX C - VCCX2 BACnet
®
VCCX2 BACnet
®
Parameters
BACnet
®
Properties for the VCCX2 Controller
Parameter
Object
Description
Limits
Unoccupied
Heating
Offset
AV: 6
During the Unoccupied
Mode of Operation, this
Setpoint offsets the
Occupied Heating
Setpoint down by this user-
adjustable amount. If you do
not want Heating to operate
during the Unoccupied
Mode, use the default setting
of 30°F for this setpoint.
0°F
0°C
30°F
16.6°C
Mode Select
Deadband
AV: 7
This value is added to and
subtracted from the HVAC
Mode Setpoints to create a
control deadband range.
0°F
0°C
10°F
5.5°C
Max Coil
Setpoint
Reset Limit
AV: 8
This is the highest that the
Coil Temperature will be
reset to during Space
Humidity Reset of the Coil
Suction Temperature
Setpoint. If no coil
temperature reset is
required, this value should
be set the same as the Min
Coil Reset Limit.
35°F
1.7°C
70°F
21.1°C
Min Coil
Setpoint
Reset Limit
AV: 9
This is the lowest that the
Coil Temperature will be
reset to during Space
Humidity Reset of the
Coil Suction Temperature
Setpoint. If no coil
temperature reset is required,
this value should be set the
same as the Max Coil Reset
Limit.
35°F
1.7°C
70°F
21.1°C
Supply Air
Cooling
Setpoint
AV: 10
Supply Air Cooling
Setpoint. If Supply Air Reset
is configured this is the Low
SAT Cooling Reset Value.
30°F
-1.1°C
80°F
26.6°C
Supply Air
Heating
Setpoint
AV: 11
Supply Air Heating
Setpoint. If Supply Air Reset
is configured this is the Low
SAT Heating Reset Value.
40°F
4.5°C
240°F
115.5°C
Max SAT
Cooling
Setpoint
Reset Limit
AV: 12
If Supply Air Reset is
configured this is the High
SAT Cooling Reset Value.
0°F
-17.7°C
100°F
37.7°C
Max SAT
Heating
Setpoint
Reset Limit
AV: 13
If Supply Air Reset is
configured this is the High
SAT Heating Reset Value.
0°F
-17.7°C
250°F
121.1°C
Supply Air
Cooling
Staging
Window
AV: 14
In Cooling Mode, if the
Supply Air Temperature
drops below the Active
Supply Air Cooling
Setpoint minus this Staging
Window, a Cooling Stage
will be deactivated after its
Minimum Run Time.
1°F
0.6°C
30°F
16.6°C
BACnet
®
Properties for the VCCX2 Controller
Parameter
Object
Description
Limits
Supply Air
Heating
Staging
Window
AV: 15
In Heating Mode, if the
Supply Air Temperature rises
above the Active
Supply Air Heating
Setpoint plus this Staging
Window, a Heating Stage
will be deactivated after its
Minimum Run Time.
1°F
0.6°C
50°F
27.7°C
Warm-Up
Target
Temperature
(See AV: 89
for Cool-
Down Target
Temperature)
AV: 16
If Morning Warm-Up is
configured, then upon
entering occupied mode,
the Warm-Up Mode will be
activated if the Return Air
is below this temperature by
one degree.
50°F
10°C
90°F
32.2°C
Warm-Up
Mode Supply
Air Setpoint
AV: 17
During Morning Warm-Up,
the Supply Air
Temperature will be
controlled to this Setpoint.
40°F
4.5°C
240°F
115.5°C
Cool-Down
Mode Supply
Air Setpoint
AV: 18
During Morning Cool-Down,
the Supply Air
Temperature will be
controlled to this Setpoint.
30°F
-1.1°C
80°F
26.6°C
Mechanical
Cooling
Outdoor Air
Lockout
AV: 19
Mechanical Cooling will be
locked out when the Outdoor
Air Temperature is below this
Setpoint.
-30°F
-34.4°C
100°F
37.7°C
Mechanical
Heating
Outdoor Air
Lockout
AV: 20
Mechanical Heating will be
locked out when the Outdoor
Air Temperature is above this
Setpoint.
-30°F
-34.4°C
150°F
65.5°C
Low Supply
Temp Cutoff
Alarm
AV: 21
Cooling will be disabled if
the Supply Air
Temperature falls below this
value. See sequence for more
details.
0°F
-17.7°C
100°F
37.7°C
High Supply
Temp Cutoff
Alarm
AV: 22
Heating will be disabled if
the Supply Air
Temperature rises above this
value. See sequence for more
details.
0°F
-17.7°C
250°F
121.1°C
Preheater
Cooling
Mode
Setpoint
AV: 23
If the Preheater is enabled,
and the unit is in the Cooling
Mode, this
setpoint will be sent to the
Preheat-X Controller to
control Leaving Air
Temperature.
35°F
-17.7°C
90°F
32.2°C
Preheater
Venting
Mode
Setpoint
AV: 24
If the Preheater is enabled,
and the unit is in the Vent
Mode, this setpoint will be
sent to the
Preheat-X Controller to
control Leaving Air
Temperature.
35°F
-17.7°C
90°F
32.2°C
Preheater
Heating
Mode
Setpoint
AV: 25
If the Preheater is enabled,
and the unit is in the Heating
Mode, this setpoint will
be sent to the Preheat-X
Controller to control Leaving
Air
Temperature.
35°F
-17.7°C
90°F
32.2°C