128
VCCX2 Controller Technical Guide
BACnet
®
Properties for the VCCX2 Controller
Parameter Object
Description
Limits
Bad Carbon
Dioxide
Sensor
BI: 16
Failure of the CO
2
Sensor.
Bad Building
Pressure
Sensor
BI: 17
Alarm indicating missing or
failed Building
Pressure Sensor.
Bad Outdoor
Airflow
Sensor
BI: 18
An Outdoor Airflow
Sensor is configured, but
not detected.
Bad Exhaust
Airflow
Sensor
BI: 19
An Exhaust Airflow
Sensor is configured, but
not detected.
Bad Supply
Airflow
Sensor
BI: 20
A Supply Airflow Sensor
is configured, but not
detected.
Bad Return
Airflow
Sensor
BI: 21
A Return Airflow
Sensor is configured, but
not detected.
Mechanical
Cooling
Alarm
BI: 22
Compressor Relays are
enabled but the Supply Air
Temperature has not fallen
5°F w/in a user-adjustable
time period. This does
not apply to Modulating
Cooling.
Mechanical
Heating Alarm
BI: 23
Heating Mode has been
initiated but the Supply Air
Temperature has not risen
5°F w/in a user-adjustable
time period. Alarms on
the MODGAS-X and
Preheat-X Controller will
generate this alarm. This
alarm does not apply to
SCR Heat, Modulating Hot
Water or Steam Heating.
Fan Proving
Alarm
BI: 24
Alarm that indicates an
Airflow failure from the
Main Fan. Heating and
Cooling will be disabled.
Dirty Filter
Alarm
BI: 25
Alarm that indicates
the filters are dirty.
Emergency
Shutdown
Alarm
BI: 26
Alarm that indicates
that Emergency Shutdown
has been activated. Will
shut the unit down.
Relay
Runtime
Warning
BI: 27
Indicates when any of the
configured relays exceeds
a configured number of
hours of runtime. Can be
used to schedule service,
etc.
Economizer
Missing
Alarm
BI: 28
Title 24 operation
indicates missing
economizer feedback.
Economizer
Title 24
Failure A
BI: 29
Title 24 Air Temperature
Sensor Failure.
Economizer
Title 24
Failure B
BI: 30
Title 24 Not Economizing
when it should.
BACnet
®
Properties for the VCCX2 Controller
Parameter Object
Description
Limits
Economizer
Title 24
Failure C
BI: 31
Title 24 Economizing when
it should not.
Economizer
Title 24
Failure D
BI: 32
Title 24 Damper Not
Modulating.
Economizer
Title 24
Failure E
BI: 33
Title 24 Excess Outdoor
Air.
High Supply
Temp Cutoff
BI: 34
The Supply Air has risen
above the Hi SAT Cutoff
Setpoint. Heating stages
will deactivate and the fan
continues to run. This alarm
is generated.
Low Supply
Temp Cutoff
BI: 35
The Supply Air has fallen
below the Low SAT Cutoff
Setpoint. Cooling stages will
deactivate. After 10 minutes,
the fan will deactivate and
this alarm is generated.
High Control
Mode Alarm
BI: 36
Occurs when the
Controlling Sensor
Temperature rises above
the Cooling Mode Enable
Setpoint plus the Control
Mode High Alarm Offset.
Applies only to Space or
Return Air Temperature
controlled units.
Low Control
Mode Alarm
BI: 37
Occurs when the
Controlling Sensor
Temperature falls below
the Heating Mode Enable
Setpoint minus the
Control Mode Low Alarm
Offset. Applies only
to Space or Return Air
Temperature controlled
units.
Missing
Refrigerant
Module #1
BI: 38
Refrigerant Module #1 is
bad or missing.
Missing
Refrigerant
Module #2
BI: 39
Refrigerant Module #2 is
bad or missing.
Missing
Refrigerant
Module #3
BI: 40
Refrigerant Module #3 is
bad or missing.
Missing
Refrigerant
Module #4
BI: 41
Refrigerant Module #4 is
bad or missing.
Missing
Preheater
Board
BI: 42
Preheater Module is bad or
missing.
Missing
Reheat Board
BI: 43
The MHGR board is
configured but not
detected.
Missing Mod
Gas Board
BI: 44
The MODGAS board is
configured but not detected.
APPENDIX C - VCCX2 BACnet
®
VCCX2 BACnet
®
Parameters