131
VCCX2 Controller Technical Guide
BACnet
®
Properties for the VCCX2 Controller
Parameter
Object
Description
Limits
Refrigerant
Module 4
Relay 4
BI: 123
Current Status of
Relay #4
Refrigerant
Module 4
Relay 5
BI: 124
Current Status of
Relay #5
Preheater
Alarm
BI: 125
Preheater Alarm Indicator
EF/RA Fan
POF
BI: 126
Exhaust Fan / Return Fan
Proof of Flow Alarm
Compressor
Running A
BI: 127
Current Run Status of
Compressor A
Compressor
Running B
BI: 128
Current Run Status of
Compressor B
Compressor
Running C
BI: 129
Current Run Status of
Compressor C
Compressor
Running C2
BI: 130
Current Run Status of
Compressor C2
Compressor
Running D
BI: 131
Current Run Status of
Compressor D
Compressor
Running E
BI: 132
Current Run Status of
Compressor E
Compressor
Running E2
BI: 133
Current Run Status of
Compressor E2
Compressor
Running F
BI: 134
Current Run Status of
Compressor F
Compressor
Running F2
BI: 135
Current Run Status of
Compressor F2
Return Fan
Proving Status
BI: 136
Proof of Return Fan Airflow
Binary Input Status
IAQ Mode
Active
BI: 137
Indicates that IAQ Mode
is active.
Heat Wheel
Defrost Active
BI: 138
Indicates Heat Wheel
Defrost is active.
VCCX2 BACnet
®
Property Identifier:
BACNETPropertyIdentifier :
VccxControlModeBits
::= ENUMERATED {
Supply Air Cooling Only
(0),
Supply Air Tempering
(1),
Outdoor Temperature Control
(2),
Return Air Constant Volume Mode
(3),
Space Temp Constant Volume Mode
(4),
Space Temp w/ High OA Content
(5),
Single Zone VAV
(6)
}
VccxControlStatusBits
::= ENUMERATED {
Unoccupied
(0)
Occupied
(1),
Override Mode
(2),
Holiday Unoccupied
(3),
Holiday Occupied
(4),
Forced Occupied
(5),
Forced Unoccupied
(6),
Remote Contact Occupied
(7)
Reserved
(8)
Reserved
(9)
Reserved
(10)
OA Damper Calibration
(11)
}
VccxHVACModeStatusBits
::= ENUMERATED {
Off
(0),
Vent Mode
(1),
Cooling Mode
(2),
Heating Mode
(3),
Vent RH Mode
(4),
Cooling RH Mode
(5),
Heating RH Mode
(6),
Warm Up Mode
(7),
Purge Mode
(8),
Defrost Mode
(9),
Cool Down Mode
(10)
}
APPENDIX C - VCCX2 BACnet
®
VCCX2 BACnet
®
Parameters