RSMZ Inputs Wiring
The RSMZ monitors and controls one refrigeration circuit of
the HVAC unit. The RSMZ is used on RZ units and on RN-E
units with Danfoss compressors. The module is designed for
R410-A refrigerant.
The RSMZ is connected to the VCCX2 Controller. Three or six
RSMZ Modules can be connected, depending on the size of the
system. There are two E-BUS Expansion Ports which allow the
use of communicating sensors and E-BUS modules. There is a
MODBUS terminal block which allows wiring to the Reheat
Expansion Module or VFD Compressor.
The RSMZ must be connected to an 18-30 VAC power source.
When wiring the RSMZ Controller, its relay outputs must be
wired as wet contacts (connected to 24 VAC). See
Figure 38,
this page
for input wiring.
WARNING:
Observe Polarity! All boards must be wired
with GND-to-GND and 24 VAC-to-24
VAC. Failure to observe polarity will result
in damage to one or more of the boards.