134
VCCX2 Controller Technical Guide
BACnet
®
Protocol Implementation Conformance Statement
Date:
December 2017
Vendor:
AAON, Inc.
Product: VCCX2
Controller
Product Model Number:
ASM01698
Product Version:
1.13
Product Description:
HVAC Unit Controller
BACnet
®
Protocol Revision: Revision 12 (ANSI/ASHRAE Standard 135-2010)
BACnet
®
Protocol Implementation Conformance Statement
K.1.2 BIBB – Data Sharing-ReadProperty-B (DS-RP-B)
K.1.4 BIBB – Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)
K.1.8 BIBB – Data Sharing-WriteProperty-B (DS-WP-B)
K.5.2 BIBB – Device Management-DynamicDeviceBinding-B (DM-DDB-B)
K.5.4 BIBB – Device Management-DynamicObjectBinding-B (DM-DOB-B)
K.5.6 BIBB – Device Management-DeviceCommunicationControl-B (DM-DCC-B)
BACnet
®
Standardized Device Profile
L.4 BACnet
®
Application Specific Controller (B-ASC)
Standard Object Types Supported
Analog Input:
Optional properties supported: Description
Analog Value:
Optional properties supported: Description
Binary Input:
Optional properties supported: Description, Inactive_Text, Active_Text
Binary Value:
Optional properties supported: Description, Inactive_Text, Active_Text
Device Object:
Optional properties supported: Description, Location
Multi-state Input:
Optional properties supported: Description, State_Text
Multi-state Value:
Optional properties supported: Description, State_Text
For all supported objects, device does not support CreateObject or DeleteObject.
There are no proprietary objects.
Data Link Layer Options
MS/TP Master: Supported Baud rates: 9.6K, 19.2K, 38.4K, 57.6K, 76.8K
Segmentation Support
Neither segmented requests nor segmented responses are supported.
APPENDIX C - VCCX2 BACnet
®
VCCX2 BACnet
®
PICS