Chapter 4: "SETPOINTS" Menu
CURRENT PROTECTION RELAY - IPR-D
Manual P/N: IPR-D GBM 01/09/2006
4.6
AUX1 OUTPUT
RELAY: LATCHED
RANGE:
........................................................................................
LATCHED; PULSED
•
PULSED
operation:
In case of fault condition due to which the related output must activate, this output will
be energized for a time as the one set in
AUX1 RELAY PULSE TIME
; after this time
the output relay will de-energize and the contact will return to the stand-by condition.
•
LATCHED
operation:
In case of fault condition due to which the related output must activate, this output will
be energized for an indefinite time. The output relay will de-energize only when the
fault condition is no more present and the unit is RESET.
AUX1 RELAY PULSE
TIME: 0.2 Sec
If
"AUX1 OUTPUT RELAY"
=
PULSED
RANGE:
.......................................................................................................
0.1 s ÷ 2.0 s
STEPS:
......................................................................................................................
0.1 s
Enter the delay for AUX 1 relay de-energizing.
AUX2 OUTPUT
RELAY: LATCHED
RANGE:
........................................................................................
LATCHED; PULSED
•
PULSED
operation:
In case of fault condition due to which the related output must activate, this output will
be energized for a time as the one set in
AUX2 RELAY PULSE TIME
; after this time
the output relay will de-energize and the contact will return to the stand-by condition.
•
LATCHED
operation:
In case of fault condition due to which the related output must activate, this output will
be energized for an indefinite time. The output relay will de-energize only when the
fault condition is no more present and the unit is RESET.
AUX2 RELAY PULSE
TIME: 0.2 Sec
If
"AUX2 OUTPUT RELAY"
=
PULSED
RANGE:
.......................................................................................................
1.0 s
÷
2.0 s
STEPS:
......................................................................................................................
0.1 s
Enter the delay for AUX 2 relay de-energizing.
AUX3 OUTPUT
RELAY: LATCHED
RANGE:
........................................................................................
LATCHED; PULSED
•
PULSED
operation:
In case of fault condition due to which the related output must activate, this output will
be energized for a time as the one set in
AUX3 RELAY PULSE TIME
; after this time
the output relay will de-energize and the contact will return to the stand-by condition.
•
LATCHED
operation:
In case of fault condition due to which the related output must activate, this output will
be energized for an indefinite time. The output relay will de-energize only when the
fault condition is no more present and the unit is RESET.
AUX3 RELAY PULSE
TIME: 0.2 Sec
If
"AUX2 OUTPUT RELAY"
=
PULSED
RANGE:
.......................................................................................................
1.0 s
÷
2.0 s
STEPS:
......................................................................................................................
0.1 s
Enter the delay for AUX 3 relay de-energizing.
END OF PAGE
Last LINE of PAGE 5.
Press
LINE
or
▲
PAGE,
to pass to the first line of PAGE 6.
For AUX3 display the information at page 4.4 “OUT OF SERVICE ON AUX 3”.
Summary of Contents for IPR-D
Page 2: ......
Page 4: ......
Page 24: ......
Page 34: ......
Page 38: ......
Page 40: ......
Page 42: ......
Page 44: ......
Page 49: ...Appendix A CURRENT PROTECTION RELAY IPR D Manual P N IPR D GBM 01 09 2006 A 5...
Page 50: ...Appendix A CURRENT PROTECTION RELAY IPR D Manual P N IPR D GBM 01 09 2006 A 6...
Page 51: ...Appendix A CURRENT PROTECTION RELAY IPR D Manual P N IPR D GBM 01 09 2006 A 7...
Page 52: ......