5. Menu
ACTUAL VALUES
VFR Voltage Frequency Relay
5.2
Instruction Manual: VFR GBM 06/10/2021
5.6 Actual values: Vbn (Vbc) HARMONICS
View the 11 Harmonics related to the phase voltage or line voltage if Delta is selected in
[6.2 Setpoints: SYSTEM SETUP: VT
Connection]
.
Vbn Harmonics
Vbn2nd= 0.0 %
…
Vbn11th= 0.0 %
(*)
Vbn Harmonics percentage values.
P
ress ▲ or ▼ to visualize all values.
If Delta VT Connection, Harmonics of Vbc will be shown.
5.7 Actual values: Vcn (Vca) HARMONICS
View the 11 Harmonics related to the phase voltage or line voltage if Delta is selected in
[6.2 Setpoints: SYSTEM SETUP: VT
Connection]
.
Vcn Harmonics
Vcn2nd= 0.0 %
…
Vcn11th= 0.0 %
(*)
Vcn Harmonics percentage values.
P
ress ▲ or ▼ in order to visualize all values.
If Delta VT Connection, Harmonics of Vca will be shown.
5.8 Actual values: FREQUENCY
Frequency
Frequency= 0.00 Hz
df/dt = 0.00 Hz/s
System Frequency value (Hz) and Frequency Variation (df/dt).
The VFR calculates frequency from voltage input
terminal 32-33
(A-B Line
voltage).
In case the metering of the line voltage cannot be done accurately, the frequency,
df/dt and frequency protection will be disabled.