4. Troubleshooting 

If the UPS system does not operate correctly, please solve the problem by using the table below.   

Symptom Possible 

cause 

Remedy 

The AC input power is not 

connected well. 

Check if input power cord 

firmly connected to the 
mains.  

No indication and alarm even 

though the main is normal.   

The AC input is connected 
to the UPS output. 

Plug AC input power cord to 
AC input correctly.   

The icon 

  is flashing and the 

warning code 

  is lighting on 

LCD display. Alarm is sounding 
every second. 

EPO function is activated.  Set the circuit in closed 

position to disable EPO 
function. 

The icon 

  is flashing and 

 

is lighting on LCD display. Alarm is 
sounding every second. 

Line and neutral conductors 

of UPS input are reversed. 

Rotate mains power socket 

by 180° and then connect to 

UPS system. 

The icon 

and 

 flashing on 

LCD display and alarm is sounding 

every second. 

The external or internal 

battery is incorrectly 

connected. 

Check if all batteries are 

connected well. 

Fault code is shown as 27 and the 
icon 

 

is lighting on LCD 

display and alarm is continuously 

sounding. 

Battery voltage is too high 

or the charger is fault. 

Contact your dealer. 

Fault code is shown as 28 and the 
icon 

 

is lighting on LCD 

display and alarm is continuously 

sounding. 

Battery voltage is too low or 

the charger is fault. 

Contact your dealer. 

UPS is overload  

Remove excess loads from 
UPS output. 

UPS is overloaded. Devices 

connected to the UPS are 

fed directly by the electrical 
network via the Bypass. 

Remove excess loads from 

UPS output. 

The icon 

 and

is flashing 

on LCD display and alarm is 

sounding twice every second. 

After repetitive overloads, 

the UPS is locked in the 
Bypass mode. Connected 

devices are fed directly by 

the mains. 

Remove excess loads from 

UPS output first. Then shut 
down the UPS and restart it.

Summary of Contents for DC1000RT

Page 1: ...Online RT RTX User Manual Online UPS 1K 1 5K 2K 3K...

Page 2: ...perating principle 4 2 3 Install the UPS 4 2 4 Setup the UPS 6 2 5 Battery Replacement 8 2 6 Battery Kit Assembly option 9 3 Operations 11 3 1 Button operation 11 3 2 LCD Panel 12 3 3 Audible Alarm 13...

Page 3: ...to UPS output sockets The UPS can be operated by any individuals with no previous experience The UPS can be operated in TN TT power distribution Connect the UPS system only to an earthed shockproof ou...

Page 4: ...e kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground...

Page 5: ...2 1 Rear panel view 1K 1 5K 2K NEMA 3K NEMA 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Input circuit breaker 5 Emergency p...

Page 6: ...onsideration the UPS is shipped out from factory without connecting battery wires Before install the UPS please follow below steps to re connect battery wires first Step 1 Step 2 Step 3 Remove front p...

Page 7: ...d external battery Tower Installation Install UPS alone Step 1 Step 2 Step 3 Install UPS and external battery NOTE When installing the UPS or battery pack with feet please keep 70mm distance from the...

Page 8: ...e also install a UL approved circuit breaker 40A between the mains and AC input in 3K model for safety operation Step 3 UPS output connection There two kinds of outputs programmable outlets and genera...

Page 9: ...Disable and enable EPO function Keep the pin 1 and pin 2 closed for UPS normal operation To activate EPO function cut the wire between pin 1 and pin 2 Step 7 Turn on the UPS Press the ON Mute button...

Page 10: ...tes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 Remove front panel Disconnect battery wires Pull out the battery box b...

Page 11: ...ssembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 3 battery kit Step 1 Remove adhesive tapes Step 2 Con...

Page 12: ...4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step...

Page 13: ...his button at least 2 seconds to turn off the UPS in battery mode UPS will be in standby mode under power normal or transfer to bypass mode if the Bypass enable setting by pressing this button Confirm...

Page 14: ...formation Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicat...

Page 15: ...voltage Vdc battery voltage Hz input frequency 3 3 Audible Alarm Battery Mode Sounding every 4 seconds Low Battery Sounding every second Overload Sounding twice every second Fault Continuously soundi...

Page 16: ...ut voltage is 240Vac For 100 110 115 120VAC models you may choose the following output voltage 100 presents output voltage is 100Vac 110 presents output voltage is 110Vac 115 presents output voltage i...

Page 17: ...is off Interface Setting ENA Bypass mode is enabled when UPS is off DIS Bypass mode is disabled when UPS is off Default 07 Programmable outlets enable disable Interface Setting ENA Programmable outle...

Page 18: ...table input voltage range is from 160V to 260V 170 270 flashing in turns The acceptable input voltage range is from 170V to 270V For 100 110 115 120 VAC models you may choose the following selection f...

Page 19: ...imizer When the input voltage is within setting range 3 Vo max UPS will bypass voltage to output for energy saving PFC and INVERTER are off at this mode Frequency Converter mode Rack When input freque...

Page 20: ...high 27 Bus unbalance 04 x Battery voltage too low 28 Bus short circuited 05 x Over temperature 41 x Inverter soft start fail 11 x Over load 43 Inverter voltage high 12 x 3 8 Warning indicator Warnin...

Page 21: ...icon and flashing on LCD display and alarm is sounding every second The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and th...

Page 22: ...D display and alarm is continuously sounding A UPS internal fault has occurred There are two possible results 1 The load is still supplied but directly from AC power via bypass 2 The load is no longer...

Page 23: ...ler Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperatur...

Page 24: ...88 peak 88 typical 90 peak Battery Mode 83 typical 86 peak 85 typical 88 peak BATTERY Battery Type 12V 9Ah 12V 9Ah 12V 9Ah 12V 9Ah Numbers 2 3 4 6 Typical Recharge Time 4 hours recover to 90 capacity...

Page 25: ...ng telephone number In the United States 1 877 385 1654 Please have the following information ready when you call Model number and Serial number Description of failure or problem Date of failure or pr...

Reviews: