1. Important Safety Warning 

Please comply with all warnings and operating instructions in this manual strictly. Save this 

manual properly and read carefully the following instructions before installing the unit. Do not 
operate this unit before reading through all safety information and operating instructions carefully 

 

1-1. Transportation 

 

Please transport the UPS system only in the original package to protect against shock 
and impact. 

 

1-2. Preparation 

 

Condensation may occur if the UPS system is moved directly from cold to warm 
environment. The UPS system must be absolutely dry before being installed. Please 
allow at least two hours for the UPS system to acclimate the environment.   

 

Do not install the UPS system near water or in moist environments. 

 

Do not install the UPS system where it would be exposed to direct sunlight or near 
heater. 

 

Do not block ventilation holes in the UPS housing. 

 

1-3. Installation 

 

Do not connect appliances or devices which would overload the UPS system (e.g. laser 
printers) to the UPS output sockets.   

 

Place cables in such a way that no one can step on or trip over them.   

 

Do not connect domestic appliances such as hair dryers to UPS output sockets.   

  The UPS can be operated by any individuals with no previous experience.   

  The UPS can be operated in TN&TT power distribution. 

 

Connect the UPS system only to an earthed shockproof outlet which must be easily 
accessible and close to the UPS system.   

 

Please use only UL-tested, UL-marked mains cable (e.g. the mains cable of your 
computer) to connect the UPS system to the building wiring outlet (shockproof outlet).   

 

Please use only UL-tested, UL-marked power cables to connect the loads to the UPS 
system.  

 

When installing the equipment, it should ensure that the sum of the leakage current of 
the UPS and the connected devices does not exceed 3.5mA. 

 

1-4. Operation 

 

Do not disconnect the mains cable on the UPS system or the building wiring outlet 
(shockproof socket outlet) during operations since this would cancel the protective earth 
of the UPS system and of all connected loads.   

 

The UPS system features its own, internal current source (batteries). The UPS output 
sockets or output terminals block may be electrically live even if the UPS system is not 
connected to the building wiring outlet.   

 

In order to fully disconnect the UPS system, first press the OFF/Enter button to 
disconnect the mains.   

 

Prevent no fluids or other foreign objects from inside of the UPS system.   

 

The EPO, RS-232 and USB circuits are an IEC 60950 safety extra low voltage (SELV) 

Summary of Contents for DC1000RT

Page 1: ...Online RT RTX User Manual Online UPS 1K 1 5K 2K 3K...

Page 2: ...perating principle 4 2 3 Install the UPS 4 2 4 Setup the UPS 6 2 5 Battery Replacement 8 2 6 Battery Kit Assembly option 9 3 Operations 11 3 1 Button operation 11 3 2 LCD Panel 12 3 3 Audible Alarm 13...

Page 3: ...to UPS output sockets The UPS can be operated by any individuals with no previous experience The UPS can be operated in TN TT power distribution Connect the UPS system only to an earthed shockproof ou...

Page 4: ...e kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground...

Page 5: ...2 1 Rear panel view 1K 1 5K 2K NEMA 3K NEMA 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Input circuit breaker 5 Emergency p...

Page 6: ...onsideration the UPS is shipped out from factory without connecting battery wires Before install the UPS please follow below steps to re connect battery wires first Step 1 Step 2 Step 3 Remove front p...

Page 7: ...d external battery Tower Installation Install UPS alone Step 1 Step 2 Step 3 Install UPS and external battery NOTE When installing the UPS or battery pack with feet please keep 70mm distance from the...

Page 8: ...e also install a UL approved circuit breaker 40A between the mains and AC input in 3K model for safety operation Step 3 UPS output connection There two kinds of outputs programmable outlets and genera...

Page 9: ...Disable and enable EPO function Keep the pin 1 and pin 2 closed for UPS normal operation To activate EPO function cut the wire between pin 1 and pin 2 Step 7 Turn on the UPS Press the ON Mute button...

Page 10: ...tes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 Remove front panel Disconnect battery wires Pull out the battery box b...

Page 11: ...ssembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 3 battery kit Step 1 Remove adhesive tapes Step 2 Con...

Page 12: ...4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step...

Page 13: ...his button at least 2 seconds to turn off the UPS in battery mode UPS will be in standby mode under power normal or transfer to bypass mode if the Bypass enable setting by pressing this button Confirm...

Page 14: ...formation Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicat...

Page 15: ...voltage Vdc battery voltage Hz input frequency 3 3 Audible Alarm Battery Mode Sounding every 4 seconds Low Battery Sounding every second Overload Sounding twice every second Fault Continuously soundi...

Page 16: ...ut voltage is 240Vac For 100 110 115 120VAC models you may choose the following output voltage 100 presents output voltage is 100Vac 110 presents output voltage is 110Vac 115 presents output voltage i...

Page 17: ...is off Interface Setting ENA Bypass mode is enabled when UPS is off DIS Bypass mode is disabled when UPS is off Default 07 Programmable outlets enable disable Interface Setting ENA Programmable outle...

Page 18: ...table input voltage range is from 160V to 260V 170 270 flashing in turns The acceptable input voltage range is from 170V to 270V For 100 110 115 120 VAC models you may choose the following selection f...

Page 19: ...imizer When the input voltage is within setting range 3 Vo max UPS will bypass voltage to output for energy saving PFC and INVERTER are off at this mode Frequency Converter mode Rack When input freque...

Page 20: ...high 27 Bus unbalance 04 x Battery voltage too low 28 Bus short circuited 05 x Over temperature 41 x Inverter soft start fail 11 x Over load 43 Inverter voltage high 12 x 3 8 Warning indicator Warnin...

Page 21: ...icon and flashing on LCD display and alarm is sounding every second The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and th...

Page 22: ...D display and alarm is continuously sounding A UPS internal fault has occurred There are two possible results 1 The load is still supplied but directly from AC power via bypass 2 The load is no longer...

Page 23: ...ler Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperatur...

Page 24: ...88 peak 88 typical 90 peak Battery Mode 83 typical 86 peak 85 typical 88 peak BATTERY Battery Type 12V 9Ah 12V 9Ah 12V 9Ah 12V 9Ah Numbers 2 3 4 6 Typical Recharge Time 4 hours recover to 90 capacity...

Page 25: ...ng telephone number In the United States 1 877 385 1654 Please have the following information ready when you call Model number and Serial number Description of failure or problem Date of failure or pr...