Office Pro UPS1000VA/1500VA Users Manual 

IMPORTANT SAFETY INSTRUCTIONS

 

SAVE THESE INSTRUCTIONS –   

This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. 

CAUTION-   

- Intended for installation in a controlled environment. 
- Maximum ambient temperature 95°F. 
- Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the      required precautions. Keep unauthorized 
personnel away from battery. 
- To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit overcurrent protection in accordance with the National 
Electric Code, ANSI/NFPA.

 

SETUP 

Inspection 

Inspect the UPS upon receipt. Notify the carrier and 
dealer if there is damage. The package is 
recyclable; save it for reuse or dispose of it properly. 
 

2 Placement 

 
 

Check the Site Wiring 
Fault Indicator 

Caution:

 If the site wiring fault indicator lights, get a 

qualified electrician to correct the building wiring. 

 
 
 

Connect the loads

 

First, connect the UPS to the AC input power 
source.    Next, plug your computer, monitor, or other 
devices into the receptacles on the rear of the UPS. 
To use the UPS as a master “On/Off” switch, make 
sure that all of the connected

 devices are switched 

“On”. 
 
 
 
 
 
 
 
 
 
 
 

Caution:

 To prevent an overloading condition, do 

not connect a laser printer to the backup outlets. 
These UPS outlets provide battery power to the 
connected equipment when utility voltage is outside 
acceptable limits. 

RJ11/RJ45 Connector 

(Optional) Provide an RJ11/RJ45 connector to 
extend the connection of telecommunication/network 
cable. 
 

Connect Computer 
Interface Port

 

(Optional) Connect the optional interface cable to 
the USB interface port on the back of the UPS. 
Connect to the computer. See software 
documentation for installation instruction.     
 

Operation Test

 

1.  Connect the UPS to the wall receptacle. 
2. Press the Power button on the front panel, verify 

that the Green Line (

) LED is on. 

3. 

Connect your computer equipment to the 
receptacles on the back of the UPS.    Unplug the 
input power cable of the UPS from the wall 

receptacle to check if the Line (

) and 

Inverter(

) LED are flashing every 2 seconds. 

Verify that the audible alarm is beeping. 

4. The ups is now running on internal battery to 

support the connected equipment. 

5. Reconnect the ups to the wall receptacle to 

complete the test.    The audible alarm will silence 
and the Green Line LED will be visible. 

6. IMPORTANT:  Plug the UPS into the wall outlet

to charge the internal battery for a minimum of 8 
hours prior to using the UPS. 

7. STORAGE: 

Store at -15 to +30 

°

C (+5 to +86 

°

F), charge the 

UPS battery every six months.   
Store at +30 to +45 

°

C (+86 to +113 

°

F), charge 

the UPS battery every three months.

 

 

 

IN

O UT

 

 

192321942005001 

 
 
 

Orion Power Systems, Inc. 

Toll-Free: 877-385-1654 

8640 Philips Hwy 

 

 

www.orionpowersystems.com 

Jacksonville, FL    32256 

 