19
Steps for setting runtime calculation ( Chart A)
Battery AH Chart
AH Rating
NP800RTX2
7AH
NP1100RTX2
9AH
NP1500RTX2
7AH
NP2000RTX2
9AH
NP2200RTX2
7AH
NP2500RTX2
7AH
NP3000RTX2
9AH
NP1100RTX2EBM
18AH
NP2000RTX2EBM
18AH
NP3000RTX2EBM
18AH
The LCD screen runtime calculation is defaulted to internal batteries. To setup the LCD
runtime calculator when adding EBMs, you must change the parameter 07: Battery total AH
setting ( see above). The total battery AH setting equals the internal battery AH rating plus the
sum of the AH rating of the EBMs. For example, an NP2000RTX2 with (2) NP2000RTX2EBM
would have a total AH rating of 45AH.
⚫
08: EPO logic setting
Interface
Setting
Set up the EPO function control logic.
AO:
Active Open (Default). When AO is selected as EPO
logic, it will activate EPO function with Pin 1 and Pin 2 in
open status.
AC:
Active Close. When AC is selected as EPO logic, it will
activate EPO function with Pin 1 and Pin 2 in close status.
⚫
00: Exit setting
Steps for setting programmable outlet
Step 1:
Before entering setting mode, the UPS should be in Stand-by
mode (off-charging) and make sure the battery is
connected. The LCD display is shown as right.