Address
Field
Description
Size
Read/write
0 x 0733
ANG(VC/VA)
VC/VA angle [from 0 (0.0°) to 3599 (359.9°)]
16 bits
Read
0 x 0734
ANG(VN/VA)
VN/VA angle [from 0 (0.0°) to 3599 (359.9°)]
16 bits
Read
0 x 0735
ANG(IA/VA)
IA/VA angle [from 0 (0.0°) to 3599 (359.9°)]
16 bits
Read
0 x 0736
ANG(IB/VA)
IB/VA angle [from 0 (0.0°) to 3599 (359.9°)]
16 bits
Read
0 x 0737
ANG(IC/VA)
IC/VA angle [from 0 (0.0°) to 3599 (359.9°)]
16 bits
Read
0 x 0738
ANG(INS/VA)
INS/VA angle [from 0 (0.0°) to 3599 (359.9°)]
16 bits
Read
0 x 0739
ANG(INC/VA)
INC/VA angle [from 0 (0.0°) to 3599 (359.9°)]
16 bits
Read
0 x 0740
INC
Calculated neutral current (Hundredths of an ampere)
32 bits
Read
0 x 0750
IA
(1)
Circuit-Breaker Direct sequence (hundredths of an ampere)
32 bits
Read
0 x 0752
IA
(2)
Circuit-breaker inverse sequence (hundredths of an ampere)
32 bits
Read
0 x 0754
IA
(0)
Circuit-breaker zero-sequence (hundredths of an ampere)
32 bits
Read
0 x 0756
ANG(IA
(1)
/VA)
IA(1)/VA angle [from 0 (0.0°) to 3599 (359.9°)]
16 bits
Read
0 x 0757
ANG(IA
(2)
/VA)
IA(2)/VA angle [from 0 (0.0°) to 3599 (359.9°)]
16 bits
Read
0 x 0758
ANG(IA
(0)
/VA)
IA(0)/VA angle [from 0 (0.0°) to 3599 (359.9°)]
16 bits
Read
0 x 0770
UAB
A-B Compound voltage (Volts)
32 bits
Read
0 x 0772
UBC
B-C Compound voltage (Volts)
32 bits
Read
0 x 0774
UCA
C-A Compound voltage (Volts)
32 bits
Read
0 x 0776
ANG(UAB/VA)
UAB/VA angle [from 0 (0.0°) to 3599 (359.9°)]
16 bits
Read
0 x 0777
ANG(UBC/VA)
UBC/VA angle [from 0 (0.0°) to 3599 (359.9°)]
16 bits
Read
0 x 0778
ANG(UCA/VA)
UCA/VA angle [from 0 (0.0°) to 3599 (359.9°)]
16 bits
Read
0 x 0780
SA
Apparent power of phase A (VAs)
32 bits
Read
0 x 0782
SB
Apparent power of phase B (VAs)
32 bits
Read
0 x 0784
SC
Apparent power of phase C (VAs)
32 bits
Read
0 x 0786
ST
Total apparent power (VAs)
32 bits
Read
0 x 0788
FPA
F.P. phase A [from 0000 (0.000) to 1000 (1,000)]
16 bits
Read
0 x 0789
FPB
F.P. phase B [from 0000 (0.000) to 1000 (1,000)]
16 bits
Read
0 x 078A
FPC
F.P. phase C [from 0000 (0.000) to 1000 (1,000)]
16 bits
Read
0 x 078B
FPT
F.P. total [from 0000 (0.000) to 1000 (1.000)]
16 bits
Read
Table 12.10.
Meterings and statuses
Meters (0 x 0AXX)
Energy (from 0 x 0A00 to 0 x 0A1F)
• Three-phase
Address
(HEX)
Field
Description
Size
Read/write
0 x 0A00
ET+
Active energy imported (in kWh) total.
32 bits
Read
0 x 0A02
ET-
Active energy exported (in kWh) total
32 bits
Read
0 x 0A04
QT1
Reactive energy Q1 (in kVArh) total
32 bits
Read
0 x 0A06
QT2
Reactive energy Q2 (in kVArh) total
32 bits
Read
0 x 0A08
QT3
Reactive energy Q3 (in kVArh) total
32 bits
Read
0 x 0A0A
QT4
Reactive energy Q4 (in kVArh) total
32 bits
Read
Table 12.11.
Three-phase
• Single-phase
Address
(HEX)
Field
Description
Size
Read/write
0 x 0A0C
EA+
Active energy imported (in kWh) phase A
32 bits
Read
0 x 0A0E
EA-
Active energy exported (in kWh) phase A
32 bits
Read
0 x 0A10
QA1
Reactive energy Q1 (in kVArh) phase A
32 bits
Read
0 x 0A12
QA2
Reactive energy Q2 (in kVArh) phase A
32 bits
Read
0 x 0A14
QA3
Reactive energy Q3 (in kVArh) phase A
32 bits
Read
0 x 0A16
QA4
Reactive energy Q4 (in kVArh) phase A
32 bits
Read