General Instructions
ekor
.rpa
Protection functions
4.8. Block by I
max
The maximum current blocking unit is implemented in
the
ekor
.rpa-100 systems, p type, used in fuse protection
cubicles, allowing the protection units to be blocked when
the line current exceeds certain set values.
Below the current set in the maximum current blocking
unit, the element in charge of protection will be the
ekor
.rpa-100 unit. On the other hand, the unit will be
blocked if the current exceeds this value, in which case the
fuses will be entrusted with protection.
If the current in any of the 3 phases is above the value set
in the maximum current blocking unit,
all protection units
will be blocked
until current drops below the set value.
The settings for this unit are not accessible by the user and
will be set by the manufacturer in accordance with the
characteristics of the cubicle where the
ekor
.rpa-100 unit
is to be installed.
1
Relay protection
2
Fuse protection
Figure 4.16.
Block by I
max