IG-267-EN versión 01; 07/04/2017
60
Protection, metering and control models
General Instructions
ekor
.rpa
Continuation
ekor
.rpa-100
Protection, metering and control units
Model
ekor
.rpa-110
ekor
.rpa-120
Type
v
p
v
p
Active/reactive/apparent power
No
No
Yes
Yes
Energy P+, P-, Q1,…,Q4
No
No
Yes
Yes
Thermal image accumulation
No
No
Yes
Yes
Temperature*
No
No
Op
Op
Check (test)
Test blocks for voltage and current injection
Yes
No
Yes
No
Communications
MODBUS-RTU
Yes
Yes
Yes
Yes
Slave PROCOME
Yes
Yes
Yes
Yes
Communications ports
Mini USB (front), local configuration with
ekor
.soft-xml
Yes
Yes
Yes
Yes
2 x Ethernet, local configuration with Web server
Yes
Yes
Yes
Yes
2 x RS-485, for remote control
Yes
Yes
Yes
Yes
* For further information please ask
Ormazabal
’s technical-commercial department
Table 8.1.
ekor
.rpa
characteristics
8.1.4. Relay configurator
The following configurator will be used to select the right
unit within the
ekor
.rpa-100 series, in accordance with the
characteristics of the installation:
Family
Range
Model
Type
Func. I>
ED/SD
I
Pwr.
V
ekor
.rpa
-120
-v
20
2
1
B
p
Table 8.2.
Configurator
Model:
• 110 – Non-directional overcurrent relay
• 120 – Directional overcurrent relay with voltage functions
Type:
• v – For protection cubicle with circuit-breaker
• p – For protection cubicle with fuses
Overcurrent protection functions:
• 10 – No protection
• 20 – Three phases, neutral (calculated) and sensitive
neutral with vector sum
• 30 – Three phases, neutral (calculated) and sensitive
neutral with zero-sequence toroidal transformers
Inputs/outputs:
• 2 – 9 inputs/4 outputs
Toroidal-core transformers:
• 0 – No toroidal-core transformers, control only
• 1 – Ratio 300/1
• 2 – Ratio 1000/1
• 4 – Ratio 2500/1
Power supply:
• B – Auxiliary power supply (Battery, UPS, etc.)
Voltage sensors
• P – Conventional/double screen bushing (in accordance
with cubicle configuration)
• EVT – Voltage sensor