GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
IG-021-GB
version 07
29.08.2008
Page 17 of 48
If they are transported vertically
(figure 3.16), they should be lifted by the short side
and placed directly in their final position (figure 3.17).
Figure 3.16
Figure 3.17
3.7.1. Assembling Bottom Plates
After checking that the ground is correctly levelled, the enclosure assembly starts by placing
the first bottom plate in its final position. Check that the plate is properly levelled by means of
a hose level.
If the enclosure consists of more than one module, insert a 20 x 10 mm adhesive rubber strip
(
reference 090006-33
) in the joint between the different bottom plates.
Figure 3.18
Figure 3.19
Great care should be taken when installing this strip, since the sealing of the Transformer
Substation depends on it.