4848
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
IG-021-GB
version 07
29.08.2008
Page 33 of 48
Put a 4 x 15 mm rubber strip around the slots where the slabs will rest (
reference
090005-22
), so that the slabs can be better settled.
Figure 3.50
The
transformer platform
locations depend on the TS configuration. Before installing them,
a 20 x 10 mm sealing rubber strip should be placed around the bottom edge.
Figure
3.51
Figure
3.52
When the transformer is to be introduced through the transformer door rather than through
the roof, the transformer platform should be located as close as possible to the door, in order
to facilitate this operation.
Next, the fire barrier tray for the platform must be put into place and adjusted with its 6
supports.
A layer of pebbles is added to the tray, to act as fire barrier.
Figure 3.53:
Fire barrier tray