IG-308-EN version 01; 03/06/2022
15
General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
Installation
4. Installation
[4]
It is advisable to cut the cellophane at the rear of the cubicle or at the corner to avoid scratching the surface.
Tightening torques:
- M8: 20 Nm
- M10: 40 Nm
4.1. Unpacking the equipment
The
cgm
.3-huv system switchgear is supplied protected by
plastic packing as standard.
On receiving the equipment, check that the goods supplied
match the order and associated documentation. If this is
not the case, contact
Ormazabal
immediately.
The disassembly process for the equipment is as follows:
1.
Use a blade, cutter or similar tool to cut the cellophane
the cubicle is wrapped in
[4]
.
2.
Completely remove the cellophane.
3.
Detach the white polystyrene corner pieces.
4.
Unscrew the fixings between the base and the pallet.
5.
Remove the pallet, handling the cubicle as indicated in
section 2.1.
6.
Unpack the accessory box located at the rear or on top
of the cubicle.
7.
Remove the self-adhesive protective plastic from the
cable compartment cover.
The self-adhesive plastic must be removed from the
cable compartment cover so that the equipment
enclosure's earth connection may have the proper
electrical continuity.
8.
Dispose of any waste in an environmentally friendly
manner.
It is advisable to make a visual inspection of the equipment
to check whether it has suffered any damage in transit. If
damaged, contact
Ormazabal
immediately.
Summary of Contents for velatia cgm.3 system
Page 75: ......