IG-308-EN version 01; 03/06/2022
20
Installation
General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
Metering function and auxiliary services
Figure 4.5.
Dimensions [mm] of the cable trench for
cgm
.3-huv ma
Trench necessary for the metering function and auxiliary services
Cable insulation
Cable type
Cable
section
[mm
2
]
Cable
diameter
[mm]
Approximate
radius of
curvature*
[mm]
Minimum depth
D2
Dry insulation
One-core 18/30 kV
< 150
41
555
600
185
43
590
650
240
45.2
640
700
300
47.5
685
750
400
48
745
800
< 150
92.7
805
850
* Check against the data of the manufacturer of the cable used.
Table 4.4.
Trench necessary for the metering function and auxiliary services
Summary of Contents for velatia cgm.3 system
Page 75: ......