IG-284-EN version 03; 06/05/2020
18
Installation
General Instructions
cgm
.800: Medium-voltage switchgear with integrated insulation in SF
6
gas
up to 36 kV in accordance with IEC Standard with rated current up to 800 A
Fuse protection function
Front and rear cable input or output (D1)
Side cable input or output (D2)
Figure 4.5.
Dimensions [mm] of the cable trench for
cgm
.800-p
Trench necessary for the fuse protection function
Cable data
Approximate
radius of
curvature*
[mm]
Minimum depth
Cable insulation
Cable type
Cable section
[mm
2
]
Cable diameter
[mm]
D1
[mm]
D2
[mm]
Dry insulation
Single-phase
< 50
35
430
500
500
70
36.5
460
550
550
95
38
500
150
41
555
600
600
Three-phase
< 95
86
735
1050
1050
* Check against the data of the manufacturer of the cable used.
Table 4.3.
Trench necessary for the fuse protection function