IG-284-EN version 03; 06/05/2020
40
Recommended sequence
of operations
General Instructions
cgm
.800: Medium-voltage switchgear with integrated insulation in SF
6
gas
up to 36 kV in accordance with IEC Standard with rated current up to 800 A
5.4.5. Opening operation from closed position
1.
Move the actuating shaft access handle in the grey
zone to its bottom position.
2. Opening operation:
a. Manual operation
(B driving mechanism).
Insert the lever in the switch access (grey area),
move the actuating arm to the end and turn anti-
clockwise 90º.
b. Motorised operation
(BR-AM/BRA-2M driving
mechanism).
Activate the corresponding operation command.
Figure 5.14.
Lever turn process
3.
Verify that the cubicle is in isolating position.
Figure 5.15.
Switch-disconnector open