IG-284-EN version 03; 06/05/2020
46
Recommended sequence
of operations
General Instructions
cgm
.800: Medium-voltage switchgear with integrated insulation in SF
6
gas
up to 36 kV in accordance with IEC Standard with rated current up to 800 A
5.5.5. Opening operation from switch-disconnector closed position
1.
The switch can be opened manually, using the push-
button on the front of the cubicle, an opening coil, or
due to action by the fuses.
Figure 5.24.
Switch-disconnector manual trip drive
2.
Verify that the cubicle is in isolating position.
Figure 5.25.
Switch-disconnector open