IG-284-EN version 03; 06/05/2020
50
Recommended sequence
of operations
General Instructions
cgm
.800: Medium-voltage switchgear with integrated insulation in SF
6
gas
up to 36 kV in accordance with IEC Standard with rated current up to 800 A
6.
Insert the fuse holder carriage in its compartment by
pulling it inward.
Before inserting the fuse holder carriage in the fuse
protection cubicle, ensure that both the carriage
as well as the inside of the fuse holder are properly
cleaned.
Figure 5.33.
Inserting the fuse holder carriage
Figure 5.34.
Inserting the fuse holder carriage
7.
Reset the fuse striker by pressing downward with the
thumb.
Figure 5.35.
Resetting the striker in the fuse holder cover