IG-284-EN version 03; 06/05/2020
55
General Instructions
cgm
.800: Medium-voltage switchgear with integrated insulation in SF
6
gas
up to 36 kV in accordance with IEC Standard with rated current up to 800 A
Recommended sequence
of operations
2. Opening operation:
a. Manual operation
.
Insert the lever in the earthing driving shaft, move
the driving arm to the end and turn anti-clockwise.
b. Motorised operation
(B2M driving mechanism).
Activate the corresponding operation command.
Figure 5.42.
Lever turn details
3.
Verify that the cubicle is in isolating position.
Figure 5.43.
Earthing switch open