IG-284-EN version 03; 06/05/2020
56
Recommended sequence
of operations
General Instructions
cgm
.800: Medium-voltage switchgear with integrated insulation in SF
6
gas
up to 36 kV in accordance with IEC Standard with rated current up to 800 A
5.7.4. Closing operation from isolating position
Initial conditions:
Earthing switch open, circuit breaker
closed and springs charged.
1.
Open the circuit-breaker by pressing the "0" button on
the front keypad and check the status indicator.
Figure 5.44.
Opening button detail
2.
Move the access handle in the grey zone to its bottom
position.
Figure 5.45.
Switch-disconnector driving shaft access handle detail.