IG-284-EN version 03; 06/05/2020
58
Recommended sequence
of operations
General Instructions
cgm
.800: Medium-voltage switchgear with integrated insulation in SF
6
gas
up to 36 kV in accordance with IEC Standard with rated current up to 800 A
5.7.5. Opening operation from closed position
Initial conditions:
Circuit breaker closed, earthing
switch open and springs charged.
1.
Open the circuit-breaker by pressing the "0" opening
button and check the status indicator.
Figure 5.48.
Opening button detail
2.
Check there is no voltage through the
ekor
.vpis or
ekor
.ivds.
3.
Move the access handle in the grey zone to its bottom
position.
Figure 5.49.
Handle detail