IG-284-EN version 03; 06/05/2020
60
Recommended sequence
of operations
General Instructions
cgm
.800: Medium-voltage switchgear with integrated insulation in SF
6
gas
up to 36 kV in accordance with IEC Standard with rated current up to 800 A
5.7.6. Earthing operation from open position
Initial conditions:
Circuit breaker open, earthing switch
open and springs charged.
1.
Close the circuit-breaker by pressing the "l" close button
and check the status indicator.
Figure 5.52.
Closing button detail
2.
Check that no voltage is present through the
ekor
.vpis
unit.
3.
Move the access handle in the yellow zone to its bottom
position.
Figure 5.53.
Handle detail