4.
Connect the terminal earth braids, if applicable, and the
cable screens.
[11]
Available for modular and compact 1300 mm cubicles.
Figure 4.49.
Earth connector
5.
Put the cable compartment cover back in place.
Rear output connection: Angled terminal
[11]
1.
Close the earthing switch.
2.
Remove the front cover to access the cable
compartment.
3.
Remove the intermediate cover (b) and take out the
cable support (a).
Figure 4.50.
Rear connection in modular cubicles up to 1300 mm high
IG-078-EN version 12; 23/04/2020
45
General Instructions
cgmcosmos
: Medium-voltage cubicles with full insulation
in SF
6
gas up to 24 kV in accordance with IEC Standard
Installation