5.4.3. Opening operation from earthing position
1.
Move the yellow slider to the right (this releases the
access so the earthing switch can be disconnected).
2.
Insert the lever in the earthing switch access, move the
actuator arm to the end and turn anti-clockwise 90º.
Figure 5.10.
Lever turn process
3.
Verify that the cubicle is in isolating position.
Figure 5.11.
Earthing switch open