IG-247-EN version 02; 08/12/2020
20
Installation
General instructions
cms
.21
2.
Once a suitable hole has been opened for the piped
conduit to be used (maximum Ø 200 mm), deburr
and introduce the conduit inside the enclosure trench
around 50 mm. The pieces of concrete should then be
removed from the interior.
Do not use polyurethane foams used for sealing.
The medium voltage cables must respect the minimum
radii of curvature indicated by their manufacturer,
both during installation and once installed.
Figure 5.9.
Introducing the cable conduit
5.5.2. Medium voltage cable connection
The connection of the medium voltage cables to the
switchgear must follow the General Instructions of the
medium voltage switchgear, supplied with the
cms
.21, in
accordance with Standards EN 50180 and EN 50181.
The maximum section of the synthetic insulation dry
single-core cables must not exceed 240/16 mm
2
and rated
voltage 18/30 kV. For other types of cables, please contact
Ormazabal
.