Installation
General instructions
cpg
.0: GIS medium-voltage switchgear,
gas insulated, up to 40.5 kV,
in accordance with IEC Standard
6.8. Cable connection
The cables are connected to the bushings with IEC type
reinforced connection connectors (screwable).
Never touch live connectors, not even screened
connectors. Screening does not constitute protection
against direct contact.
When the equipment is in service and a back-up cubicle
is left with voltage in the upper busbar and without
cables in the bottom bushings, insulating plugs must
be placed on the bushings or the disconnector must be
placed in earthing position, and locked in its position
with a padlock.
The recommended connectors are detailed below.
Cubicle
model
Manu-
facturer
Connector Connector
series
Nº
terminals
Terminal
configuration
Max. rated
current
connector
[A]
Total
connector
length
[mm]
Max. diameter
on insulation
admitted by
the connector
[mm]
cpg
.0-v 24 kV
25 kA 630 A
Nexans
EUROMOLD
Screened
400TB
1 cable
400TB + CUP
800
255
37.5
440TB
1 cable
440TB + CUP
1250
255
56
480TB
1 cable
480TB + CUP
1250
185
40.5
1 cable + SA
480TB + 800SA + CUP
1250
290
40.5
484TB
1 cable
484TB + CUP
1250
185
56
1 cable + SA
484TB + 800SA + CUP
1250
290
56
Continued on next page