IG-123-EN version 11; 23/07/2021
35
General instructions
cpg
.0: GIS medium-voltage switchgear,
gas insulated, up to 40.5 kV,
in accordance with IEC Standard
Installation
Continuation
Cubicle
model
Manu-
facturer
Connector Connector
series
Nº
terminals
Terminal
configuration
Max. rated
current
connector
[A]
Total
connector
length
[mm]
Max. diameter
on insulation
admitted by
the connector
[mm]
cpg
.0-f/fl
Nexans
EUROMOLD
Screened
400TB
1 cable
400TB + CUP
800
255
37.5
1 cable + SA
400TB + 400PB-10SA
+ CUP
800
410
37.5
440TB
1 cable
440TB + CUP
1250
255
56
1 cable + SA
440TB + 400PB-10SA
+ CUP
1250
410
56
480TB
1 cable
480TB + CUP
1250
185
40.5
1 cable + SA
480TB + 800SA + CUP
1250
290
40.5
484TB
1 cable
484TB + CUP
1250
185
56
1 cable + SA
484TB + 800SA + CUP
1250
290
56
cpg
.0-vl,
cpg
.0-fl
side bushing
Nexans
EUROMOLD
Screened
400TB
1 cable
400TB + CUP
800
255
37.5
440TB
1 cable
440TB + CUP
1250
255
56
480TB
1 cable
480TB + CUP
1250
185
40.5
2 cables
480TB + 804PB + CUP
1250
295
40.5
484TB
1 cable
484TB + CUP
1250
185
56
2 cables
484TB + 804PB + CUP
1250
295
56
Table 6.3.
Recommended connectors
Summary of Contents for velatia cpg.0