General Instructions

ekor.gid 

Main components of ekor.gid 

3.1.  Enclosure 

3.1.1.  Wall-mounted

The exterior enclosure of the ekor.gid unit is made of metal 

in order to achieve an improved mechanical protection 

and greater rigidity. This ensures a greater protection of 

its internal components against handling accidents such 

as dropping the unit and external impacts, or accidents 

once the unit is installed at its final location. Also, internal 

components, whose weight require them to be securely 

fastened to the structure, can be installed at the factory. 

In accordance with current regulations, the ekor.gid 

Smart Distribution Management Unit has reduced depth 

dimensions so it can be installed without obstructing the 

operational clearance of the Transformer or Switching 

Substations.

It has two independent and removable doors to allow 

proper access to its interior in areas with reduced space. 

This allows for optimum operation of its components under 

any circumstance.

Its interior is divided into two clearly differentiated areas or 

compartments, which are accessed via each of the doors: 

•  The top area, Communications Compartment, houses 

the communication components and the batteries. All 

the components are connected to a protective earth and 

therefore they can be directly accessed for maintenance, 

configuration, etc.

•  The lower area, Low Voltage Compartment, houses 

the Low Voltage components like the power supply 

equipment, PLC concentrator, Low Voltage Monitor(s), 

Ethernet gateway and each of their different connection/

protection components. These components are 

referenced to the Low Voltage neutral potential and 

are integrated inside polycarbonate, providing a 10 kV 

insulation that does not allow accessing them if they 

have not been previously disconnected, in order to 

ensure the safety of the operators.

The cabinet incorporates non-forced ventilation by means 

of side grilles for proper circulation of the air and the heat 

generated by the different components. 

Since this is a cabinet with a metallic structure, the fire load 

is minimal.

3.1.2.  Cubicle-mounted

The exterior enclosure of the ekor.gid-s unit is metal, using 

the same fastening and support elements as those designed 

for other cabinets installed on cubicles. Mechanical 

protection is therefore maintained, along with improved 

rigidity. This ensures a greater protection of its internal 

components against handling accidents such as dropping 

the unit and external impacts, or accidents once the unit 

is installed at its final location. Also, internal components, 

whose weight require them to be securely fastened to the 

structure, can be installed at the factory. 

The  ekor.gid-s cubicle-mounted Smart Distribution 

Management Unit uses the space on the cubicle to 

integrate the telemanagement and communications 

solutions without having to occupy the operating clearance 

in Transformation or Switching Substations, in accordance 

with current regulations.

The interior is defined in two zones or compartments which 

are accessed from the front of the cubicles, straightforwardly 

and close to the door: 

•  The exterior zone, namely the Communications 

Compartment, houses the communication elements on 

the door. A volume has been defined which allows the 

installation of different communication solutions, as well 

as the communications antenna. All the components are 

connected to a protective earth and therefore they can 

be directly accessed for maintenance, configuration, etc.

•  The interior, Low Voltage Compartment, houses the Low 

Voltage Remote Management components like the PLC 

concentrator, Low Voltage Monitor(s), Ethernet gateway 

and each of their different connection/protection 

components. These components are referenced to 

the Low Voltage neutral potential and are integrated 

inside polycarbonate, providing a 10 kV insulation that 

does not allow access if they have not been previously 

disconnected, in order to ensure the safety of operators.

The cabinet incorporates non-forced ventilation by means 

of rear grilles for proper circulation of the air and the heat 

generated by the different components. 

Since this is a cabinet with a metallic structure, the fire load 

is minimal.

Summary of Contents for velatia ekor.gid

Page 1: ...LIB ekor gid Smart distribution management unit General Instructions IG 175 EN version 02 17 06 2016...

Page 2: ...trical installations This personnel must be fully familiar with the instructions and warnings contained in this manual and in other recommendations of a more general nature which are applicable to the...

Page 3: ...4 4 Low Voltage Monitor s 17 3 4 5 Power Supply Equipment depending on the model 17 3 4 6 Ethernet 18 3 4 7 Connection and Protection Components 19 3 5 ekor gid unit interconnections 19 3 5 1 Telemana...

Page 4: ...ults in fewer errors on site 2 Scalability of the investment The items required for Telemanagement can be installed at an initial phase Subsequently it is possible to add the rest of components requir...

Page 5: ...sses the electrical characteristics of Medium Voltage consumption alarms from the Transformer Substation and faults 4 Automation of the Medium Voltage network 5 Communications This acts as a communica...

Page 6: ...future This is especially the case using the Ethernet communication ports that are available in the communication components of the ekor gid unit 2 2 Monitoring of the Low Voltage network 2 2 1 Basic...

Page 7: ...tivity Possibility of fuse temperature detection Figure 2 3 Fuse detail in Low Voltage board The Advanced Monitoring of the Low Voltage network is implemented using sensors in the Low Voltage fuses of...

Page 8: ...ci unit whose primary purpose is the Monitoring of the Medium Voltage network 1 IEC 60870 5 104 Communications 2 VDC 3 PLC Low Voltage Communications Figure 2 4 ekor gid communication with the Medium...

Page 9: ...he location of damages inside the Electrical network 2 Refer to Ormazabal s IG 177 General Instructions document for cgmcosmos 2lpt Compact Cubicle with Integrated Remote Control Unit 3 Metering of th...

Page 10: ...ation with the Customer Management Centre or the dispatching Centre 1 GPRS 2 PLC Medium Voltage 3 Optical Fibre 4 Radio Isolated communication of the Low Voltage network is possible thanks to the oper...

Page 11: ...nit are shown below 1 Communications Compartment 2 Low Voltage connections compartment 3 Interior enclosure interlock system Low Voltage Access 4 Connection protection and power supply components 5 Co...

Page 12: ...the following layout of elements of the ekor gid Smart Distribution Management Unit 1 Auxiliary terminals 2 Low Voltage Monitor 3 Concentrator 4 ED Module 5 ED Terminals 6 GPRS Modem 7 GPRS Antenna 8...

Page 13: ...e different components Since this is a cabinet with a metallic structure the fire load is minimal 3 1 2 Cubicle mounted The exterior enclosure of the ekor gid s unit is metal using thesamefasteningand...

Page 14: ...ing Substation In this case the Substation includes an ekor uct Remote Control Compact Unit or a cgmcosmos 2lpt Compact Cubicle with Integrated Remote Control Equipment that allows carrying out the fu...

Page 15: ...mm thick sheet 4 Very light weight with a density of 1 2 3 6 kg m2 Half of that of glass 5 Temperature performance limit 80 C without deformation Thispolycarbonateenclosureguaranteescompleteisolation...

Page 16: ...enced to the Low Voltage neutral potential Since the enclosure of the ekor gid s unit is at protective earth potential all the components are integrated on polycarbonate to prevent insulation problems...

Page 17: ...unication components and they send the information from these to the Customer Management Centre 3 4 5 Power Supply Equipment depending on the model The power supply unit is a component connected to th...

Page 18: ...Receiver for Advanced Monitoring of the Low Voltage network 2 MODBUS master 3 10 kV insulation Advanced monitoring of the Low Voltage network 1 Radio Receivers The radio receivers implement the follo...

Page 19: ...e outputs 3P N and 6 current outputs Ia1 Ia2 Ib1 Ib2 Ic1 Ic2 for each Low Voltage board to be monitored The voltage signals are wired to miniature circuit breakers and in the case of current signals t...

Page 20: ...and a hub for the Ethernet connector This component which is housed in the Communications compartment of the ekor gid unit separates and isolates the communications of the power supply and distribute...

Page 21: ...hese Low Voltage sensors are the following 1 The installation of the sensors can be carried out on the existing Low Voltage network they can be installed on the standard fuses 2 The sensors do not req...

Page 22: ...Interior Wall Mounted Distribution Management Unit does not include a power supply unit since it is oriented towards Automated Substations where the power is provided by the ekor uct unit or the cgmc...

Page 23: ...of Low Voltage is carried out 4 3 Interior cubicle mounted ekor gid s The ekor gid s interior cubicle mounted Smart Distribution Management Unit has the following main functions 1 Telemanagement 2 Mo...

Page 24: ...Distribution Management Unit uses the safe power of the charger with batteries benefiting from its layout close to the cubicle mounted automation Additionally this Basic ekor gid unit can carry out th...

Page 25: ...nsions Communications Compartment ekor gid i S Basic mm 337 497 147 ekor gid i L Standard mm 487 497 147 ekor gid s mm 300 300 250 Weight kg 40 Weight kg 30 IP Rating according to UNE 20324 IP3X ekor...

Page 26: ...ation install the lugs on the ekor gid unit protruding to the left right or protruding upwards downwards 2 Drill the holes corresponding to the lugs using as the lower reference point a height of 1000...

Page 27: ...upports have a pair of screws for height adjustment 2 Bolt the supports to the side lugs of the cubicle 3 Remove the cover from the cubicle s control 4 Place the cabinet on the cubicle using the cubic...

Page 28: ...dium Voltage network relays which come out of a packing gland in the Communications Compartment of the ekor gid unit and go to the Monitoring cubicle This circuit is protected by a miniature circuit b...

Page 29: ...ithout any connections is recommended 2 6 current outputs Ia1 Ia2 Ib1 Ib2 Ic1 Ic2 of each Low Voltage board to be monitored and therefore for each Medium Low Voltage transformer available in the Subst...

Page 30: ...wer comes from the ekor uct or cgmcosmos 2lpt cubicle mounted model A With power supply equipment and batteries Low Voltage Monitors 1 Low Voltage Monitoring of the Low Voltage network a single Medium...

Page 31: ......

Page 32: ...Subject to change without prior notice For further information contact Ormazabal Ormazabal Protection Automation IGORRE Spain www ormazabal com...

Reviews: