background image

VENTILATION FAN

WARNING

READ AND SAVE THESE INSTRUCTIONS

Installer: Leave this manual with the homeowner.

CAUTION

CLEANING & MAINTENANCE

OPERATION

TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:

1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the 

    address or telephone number listed in the warranty.

2. Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent 

    power from being switching on accidentally. When the service disconnecting means cannot be locked, securely fasten

    a prominent warning device, such as a tag, to the service panel.

3. Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and 

    standards, including fire-rated construction codes and standards.

4. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equip-

    ment to prevent backdrafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those

    published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and 

    Air Conditioning  Engineers (ASHRAE), and the local code authorities.

5. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.

6. Ducted fans must always be vented to the outdoors.

7. Acceptable for use over a tub or shower when connected to a GFCI (Ground Fault Circuit Interrupter) - protected branch

    circuit (ceiling installation only).

8. This unit must be grounded.

1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.

2. This product is designed for installation in ceilings up to a 12/12 pitch (45 degree angle). Duct connector must point up.

    DO NOT MOUNT THIS PRODUCT IN A WALL.

3. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off

    power unit.

4. Please read specification label on product for further information and requirements.

For quiet and efficient operation, long life, and attractive appearance - lower or remove grille and vacuum interior of unit

with the dusting brush attachment.

The motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive or unusual noi-

ses, replace the motor with the exact service motor. The impeller should also be replaced.

Use an on/off switch to operate this fan. See “Connect Wiring” for details.

For model OD-5006HS OD-8011HS

The humidity control and fan can be operated separately. Use a 1 or 2 function wall control. Do not use a dimmer switch 

to operate the humidity control or light. See “Connect Wiring” for details.

SENSOR OPERATION

The humidity-sensing fan uses a sophisticated humidity sensor that responds to: (a) rapid to moderate (user-adjustable)

increases in humidity or (b) humidity above a user-adjustable set-point (50%-100% relative humidity). The humidity sen-

sor may occasionally turn the fan ON when environmental conditions change. If the fan continuously responds to chang-

ing environmental conditions, “H” (means “humidity”) adjustment may be required. This figure is factory-set for about 75%

(Ambient temperature of 25

)

.

SENSITIVITY

 

ADJUSTMENT

The “H” has been factory set for most shower applications. However, if the fan is in a tub area or is being used for damp-

ness control, the “H” may need to be increased toward maximum “+”. If the control is responding too often to changing 

environmental conditions, movement toward less “-” “H” may be required.

To adjust the “H”:

1. Disconnect power at service entrance.

2. Through the grille, locate the slot marked “H”.

3. Carefully rotate the “H” adjustment toward “+” or “-”.

OD-5006

OD-5006HS

OD-8011

OD-8011HS

Summary of Contents for OD-5006

Page 1: ...ion in ceilings up to a 12 12 pitch 45 degree angle Duct connector must point up DO NOT MOUNT THIS PRODUCT IN A WALL 3 To avoid motor bearing damage and noisy and or unbalanced impellers keep drywall...

Page 2: ...operation by turning on the shower or other humidity source until the fan turns on 5 Repeat above steps if necessary When the temperature changes humidity sensor values will have deviation TIMER ADJU...

Page 3: ...m of the housing is even with the finished ceiling Extend the hanger hars to the joist Use screws to secure the hanger bars to the ceiling joists DUCT 3 ATTACH DAMPER DUCT CONNECTOR Snap the damper du...

Page 4: ...ssembly Grille Spring Blower Assembly includes part 3 6 7 Replacement installation Remove the screw on motor plate part 3 then take out the motor plate part 3 from the housing part 9 by pushing down t...

Page 5: ...OD 5006 OD 5006HS OD 8011 OD 8011HS Four Model OD 5006HS OD 8011HS VENTILATEUR AVERTISSEMENT PRECAUTION L ENTRETIEN ET LE NETTOYAGE FONCTIONNEMENT 5...

Page 6: ...ez l chement le bo tier la solive en ins rant des vis bois dans les encoches en trou de serrure des languettes de montage R glez la position du bo tier de fa on ce qu il soit au m me niveau que le pla...

Page 7: ...UR L ASSEMBLAGE 2 INSTALLATION AVEC BARRES DE SUSPENSION Ins rez les barres de suspension dans les fentes du bo tier Placez le bo tier du ventilateur entre les solives de fa on ce que le bord inf rieu...

Page 8: ...t de pi ces Enlevez la vis puis retirez la plaque du moteur pi ce 3 du bo tier en poussant la nervure vers le bas tout en tirant sur le c t du bo tier pi ce 9 Remplacez les pi ces d fectueuses PI CE N...

Reviews: