13
!
WARNING
Constant voltage present in the junction box. Be-
fore any electrical work is done, the power supply
must be disconnected and secured against acti-
vation while the work is in progress.
5.2 Maintenance
5.1 Settings
5.1.1 Thermostat setting
The product’s thermostats are adjustable from
60-90°C. The thermostat should not be set lower
than 65°C to prevent bacteria growth. To adjust
the temperature:
A) Disconnect the power supply.
B) Remove the cover (2) with a screwdriver.
C) Adjust the temperature on the thermostats (3)
with a screwdriver.
Fit the cover (2) before connecting the power sup-
ply.
5.1.2 Resetting the safety thermostat
The safety thermostats on the product cut out
when there is a risk of overheating. These are re-
set by switching off the power supply, removing
the cover (2) and pressing the red ‘RESET’ button
(4). If the thermostat cuts out repeatedly, contact
the installer.
5. USER GUIDE
RESET
RE
SET
M2
1
2
3
4
THERM-O-DISC
60°C
90°C
80°C
70°C
1
2
3
4
MAINTENANCE INSTRUCTIONS
!
Maintenance should be carried out by persons over 18 years of age, with suf-
ficient understanding.
!
Annual inspection of safety valve:
- Open valve for 1 min. by turning the knob (1) approx. 90 degrees to the open
position.
- Visually check that the water is flowing freely to the drain.
- YES = OK. Close the valve by pushing the lever (1) down to the closed position.
- NO = NOT OK. Disconnect power supply / shut off water supply. Contact in-
staller.
1