background image

Operation 

________________________________________________________________________________  

OSRAM operating instructions DALI Repeater LI 

page 6

 

Functional test 

The functional test allows checking proper operation of all DALI devices connected to the output: 

With every short push (< 0.5 s) on the integrated "Service“ button of the DALI REPEATER LI the 
switching state is toggled between on (max. brightness) and off. Please ensure that all connected 
DALI devices react correspondingly. Approximately 5 s after the last „Service“ button press, the 
DALI REPEATER LI return to normal operation automatically. 

As long as the functional test is active the indication LED of the repeater flashes alternating between 
green and yellow.  

Service button 

The integrated service button of the DALI REPEATER LI provides following functionality: 

 

During initialise process the highest minimal dimming level of the connected DALI devices is 
detected and stored. It is started by pressing the integrated “service” button for at least 0.5 s. 

 

Physical selection during address assignment, by a short press (< 0.5 s) on the service button. 

 

Activation of the functional test, by a short press (< 0.5 s) on the service button during normal 
operation.

 

Hint: 

Physical selection is used/supported by some control units only, for details please refer to the 
operation instructions of the corresponding control unit. 

 

 

Summary of Contents for DALI Repeater LI

Page 1: ...III 2008 DALI Repeater LI 001240508GB ZPE 2433444 OSRAM GmbH www osram com ecg lms Customer Service Center CSC www osram de evg lms Steinerne Furt 6286167 Augsburg Germany Tel 49 1803 677 200 charges apply Fax 49 1803 677 202 ...

Page 2: ...unting e g for recessed ceiling installation is suitable Safety information The following information is provided for your safety Please read these operating instructions carefully before installing and using the DALI REPEATER LI This is the only way to ensure that you use the equipment safely and correctly Keep these operating instructions in a safe place for future reference You should make sure...

Page 3: ... DALI ECG or further repeaters For maximum number of DALI devices please refer to the instructions of the control unit Maximum wire length at the output of the DALI Repeater is 300 m in total over both outputs Both outputs of the DALI Repeater LI are electrically interconnected To simplify the connection the layout is done by pairs Outputs of different Repeaters may not be interconnected with each...

Page 4: ...rminals must not be connected The maximal overall wire length at the push button input should not exceed 100 m Further points of control can be achieved by parallel connection of several push buttons Push buttons with glow indication lamps in parallel to the push to make contact are inapplicable Both outputs of the DALI Repeater LI are electrically interconnected To simplify the connection the lay...

Page 5: ...tion LED and Service button Touch DIM operation Before first manual operation the DALI Repeater should be initialised as follows Initialise is started by pressing the integrated service button of the DALI REPEATER LI for at least 0 5 s During initialise process the highest minimal dimming level of the connected DALI devices is detected and stored During this process the LED will flash in yellow Af...

Page 6: ...n automatically As long as the functional test is active the indication LED of the repeater flashes alternating between green and yellow Service button The integrated service button of the DALI REPEATER LI provides following functionality During initialise process the highest minimal dimming level of the connected DALI devices is detected and stored It is started by pressing the integrated service...

Page 7: ... activated by a short press on the service button flashing red green No DALI device at the output detected Broken wire connection at the output side or interruption of mains supply of the connected DALI devices yellow Lamp failure At least one of the connected DALI devices is indicating a lamp fail flashing yellow Initialising detection of highest minimal dimming level Initialise process was start...

Page 8: ...p to 2 Touch DIM RC 4008321183033 Maintenance free battery less EnOcean transmitter technology inductive power generation Technical data Designation DALI REPEATER LI Supply voltage 100 240 V 50 60 Hz or DC Power consumption Depends on number of connected DALI devices max 4 W Control input DALI acc IEC 62386 102 201 DALI output max 64 DALI ECG respectivly max 130mA Wire cross section 0 5 1 5 mm 2 A...

Reviews: