OPTIONS via add on module EXP-1
(9050054)
The following features are optional and are not included in the basic version supp-
lied from H. Östberg AB.
Besides the respective sensor, an EXP1 is also required to obtain multiple I/Os
(inputs/outputs).
PRESSURE REGULATION
Duct pressure regulation, designed to be combined with VAV systems. The fans are
controlled to maintain a pre-set pressure (setpoint), via
GP1
and
GP2
, in each duct
system.
FLOW REGULATION
Flow regulation is designed to be used in systems where a constant flow is desired. The
fans are controlled to maintain a pre-set flow (setpoint), e.g. compensate for increased
filter clogging via
GF1
and
GF2
.
PRESSURE REGULATION WITH FLOW MEASUREMENT
This function can also be combined with one fan operating as MASTER/duct pressure
regulation and the other fan as SLAVE/flow regulated.
MASTER-/SLAV regulation requires
GP1/GP2, GF1
and
GF2
.
FAN COMPENSATION
Fan compensation can be obtained via air quality/humidity sensor
GQ1/GM1
(duct or
room model). The fan can be boosted to a higher flow at higher PPM/RH.
ALARMS
• Deviation alarm:
GT1, GT2, GT3, GP1, GP2, GP3, GP4, GF1 and GF2
• Recovery alarm
(rotor control EMS)
• Fan alarm
• Freeze protection sensor
GT8/
Overheating
electric heater GT9
• Low efficiency
MULTIFUNCTIONAL INPUT
The following functions are located at the same signal input and cannot be combined:
–
Control input 1:
Timer input for additional speeds.
–
Control input 2:
Additional speeds from BMS.
–
Quick stop input
–
Common filter alarm:
Active via pressure sensor, supplied as optional accessory.
EFFICIENCY MEASUREMENT EXTRACT AIR
Temperature efficiency is calculated via temperature sensors
GT2
,
GT42
and
GT3
,
provided that the heat exchanger signal is 100%.
Alarm is triggered if efficiency falls below the set value.
FIRE/SMOKE
When a signal is received from the parent fire/smoke system, the fire/smoke alarm will
not be triggered.
In the event of alarm, the following functions can be selected:
• The unit is stopped and the damper closes.
• Extract fan speeds up to the fire setpoint and supply fan is stopped.
Dampers
ST1/ST2
remains open.
• Supply fan speeds up to the fire setpoint and extract fan is stopped.
Dampers
ST1/ST2
remains open.
• extract fan speed up to the fire setpoint. Dampers
ST1/ST2
remains
open
.