10 / 120
Climatix HERU® 400-2400
2018-02-13
Scope of assembly/installation instructions
•HERU
is suitable for placement in warm areas.
INSTALLATION AND SAFETY
USE
•
For optimal indoor climate and to avoid moisture damage in the property, there must be
continuous and adequate air exchange. The unit must be run continuously and only
stopped for service. Airflow is controlled via various settings on the control panel:
Reduced
–
Reduced airflow, can be used when no one is in the property.
Normal
–
This is set by the installer and should not be changed by the user.
Boost
–
Higher airflow than normal, medium/max can be selected. This should be used
when the load on the property is higher than what the standard mode is set for, e.g. when
there are more people than normal in the property.
•
When installing HERU®, follow applicable regulatory requirements and
recommendations concerning location, access, duct insulation, etc.
•
The user may, in accordance with IEC 60335-2-40, independently perform the service
and maintenance on Heru that is described in this user manual. However, the unit must be
disconnected from any power supply before all such work. With reservation according to
IEC 60335-2-7.12
“This
appliance is not intended for use by persons (including children)
with reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning use of the
appliance by a person responsible for their safety. Children should be supervised to ensure
that they do not play with the
appliance.”
•
HERU® should be kept in a sheltered and dry environment during storage before
installation.
•
Dimensioned airflow should not exceed 75% of the
unit’s
maximum capacity.
•
Check regularly to ensure that supply air and extract air are functioning properly.
•
To avoid condensation in the unit in cold weather, the unit should not be turned off for a
prolonged period of time. If the unit is installed during cold weather and not operated
immediately, the ducts should be plugged to prevent condensation.
SAFETY
•
Maintenance and operation of the unit may only be performed by personnel who have the
requisite knowledge concerning maintenance of the ventilation unit and who have read this
manual.
•
Take into account the
unit’s
weight when installing. See technical specification for
weight data.
•
Bear in mind that HERU® and the fan housing may have sharp corners and edges.
•
Before commissioning, make sure there are no foreign objects inside the unit which could
cause serious injury or damage to the unit.
•
Always follow the electrical safety regulations concerning free clearance for control
cabinets and electric heating coils.
•
Make sure that the unit is always locked and that the keys are stored in a location that is not
accessible to unauthorized persons.
•
Do not open the service doors while the unit is in operation. Overpressure from the fans
could cause the doors to swing open.
•
The unit should be fitted with a locking safety switch placed nearby.
•
Turn off the unit via the control panel and wait two (2) minutes before opening the service
doors.
•
The safety switches must be switched off and locked before starting any service
work.
Summary of Contents for HERU 400-2400 S
Page 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Page 2: ......
Page 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Page 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Page 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Page 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Page 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Page 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Page 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Page 119: ......
Page 120: ......