101 / 120
2018-02-13
Climatix HERU® 400-2400
SERVICE HERU®
The hinges are adjustable. The lock plate and guide on the casing should be greased
every 12 months.
Damper
The safety switches must be switched off and locked after the unit has been switched off
before starting any service work.
Function
Normally, the function of the damper is to close off the airways at the outside air and
exhaust air ducts when the unit is switched off. It is important for operating and energy
reasons that the damper works properly.
Check controls
1. Check visually, e.g. through the filter part or another inspection hatch, that the
damper completely seals when the unit is switched off using the normal On/Off
function. (Not with switch disconnector).
2. Make sure the damper opens and closes by starting and stopping the unit.
3. Make sure the sealing strips on the damper blades are intact.
Corrective action
1. Adjust the damper blade and actuator until the blade fully seals.
2. Check the control equipment to make sure everything is correctly connected.
3. Change the sealing strips if needed.
NOTE: Never drill or screw in the end of the damper where the motor shelf and shaft
ends are located.
Rectangular damper
Circular damper.
Summary of Contents for HERU 400-2400 S
Page 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Page 2: ......
Page 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Page 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Page 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Page 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Page 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Page 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Page 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Page 119: ......
Page 120: ......