102 / 120
Climatix HERU® 400-2400
2018-02-13
SERVICE HERU®
Duct cooling coil
The safety switches must be switched off and locked after the unit has been switched off
before starting any service work.
Function
The air cooler uses water to cool the supply air to the desired outgoing temperature. The
cooler consists of a number of copper pipes with aluminium slats. For circulation and
regulation of the water, the cooler is usually equipped with a shunt group. Condensation
usually forms on the cooler, which is therefore fitted with a tray and drainage. A water
trap with a non-return valve should be connected to the drainage.
Check
1. That the front surface of the coil is not dirty.
2. That the pump is running and that the water is circulating and has the correct
temperature for the season.
3. That the slats are intact.
4. That the coil is not damaged and is not leaking.
5. That the drainage tray is free of contamination.
6. That the water trap is working and is full of water
Corrective action
1. Clean with a vacuum cleaner fitted with a soft brush.
2. Check the pump for damage. Make sure the sensor is working.
3. Adjust the slats with a “slat comb”.
4. Turn off the water and empty the system through the coil’s drain valve. Change the
coil.
5. Clean. If necessary, adjust the coil’s incline toward the condensation pipe.
6. Make sure the ping-pong ball can move freely and is not stuck.
Duct cooling coil
Water trap.
Summary of Contents for HERU 400-2400 S
Page 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Page 2: ......
Page 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Page 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Page 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Page 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Page 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Page 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Page 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Page 119: ......
Page 120: ......